6ES7153-2BA10-0XB0
Product category
Interface modules (ET 200M)Manufacturer
SIEMENSProduct series
S7-300| General information | |
|---|---|
| Product type designation | IM 153-2 DP HF |
| Firmware version | V6.0.0 |
| Vendor identification (VendorID) | 801Eh |
| Supply voltage | |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| external protection for power supply lines (recommendation) | 2,5 A |
| Mains buffering | |
| Mains/voltage failure stored energy time | 5 ms |
| Input current | |
| Current consumption, max. | 650 mA; with 24 V DC supply |
| Inrush current, typ. | 3 A |
| I²t | 0.1 A²·s |
| Output current | |
| for backplane bus (5 V DC), max. | 1.5 A |
| Power loss | |
| Power loss, typ. | 5.5 W |
| Address area | |
| Address space per module | |
| Inputs | 244 byte |
| Outputs | 244 byte |
| Hardware configuration | |
| number of modules per DP device interface, max. | 12 |
| Time stamp | |
| Accuracy | 1 ms; 1 ms at up to 8 modules; 10 ms at up to 12 modules |
| Number of message buffers | 15 |
| Messages per message buffer | 20 |
| Number of stampable digital inputs, max. | 128; Max. 128 signals/station; max. 32 signals/slot |
| Time format | RFC 1119 |
| Time resolution | 0.466 ns |
| Time interval for transmitting the message buffer if a message is present | 1 000 ms |
| Time stamp on signal change | rising / falling edge as signal entering or exiting |
| Interfaces | |
| Transmission procedure | RS 485 |
| Transmission rate, max. | 12 Mbit/s |
| 1. Interface | |
| automatic detection of transmission rate | Yes |
| Interface types | |
| Output current of the interface, max. | 70 mA |
| Design of the connection | 9-pin sub D socket |
| PROFIBUS DP device | |
| GSD file | SI05801E.GSG |
| automatic baud rate search | Yes |
| Protocols | |
| Bus protocol/transmission protocol | PROFIBUS DP to EN 50170 |
| Protocols (Ethernet) | |
| TCP/IP | No |
| PROFIBUS DP | |
| Number of node addresses, max. | 1 to 125 permitted |
| Services | |
| SYNC capability | Yes |
| FREEZE capability | Yes |
| Direct data exchange (slave-to-slave communication) | Yes; as publisher with all IO, as subscriber with F-IO only |
| Potential separation | |
| Potential separation exists | Yes |
| Isolation | |
| Isolation tested with | Isolation voltage 500 V |
| Degree and class of protection | |
| IP degree of protection | IP20 |
| Ambient conditions | |
| Ambient temperature during operation | |
| min. | 0 °C |
| max. | 60 °C |
| horizontal installation, min. | 0 °C |
| horizontal installation, max. | 60 °C |
| vertical installation, min. | 0 °C |
| vertical installation, max. | 40 °C |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 3 000 m |
| Configuration | |
| Configuration software | |
| STEP 7 | Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 117 mm |
| Weights | |
| Weight, approx. | 360 g |
| Approvals / Certificates | |