6ES7322-5SD00-0AB0
Product category
Digital modulesManufacturer
SIEMENSProduct series
S7-300| Supply voltage | |
|---|---|
| Load voltage L+ | |
| Rated value (DC) | 24 V |
| Reverse polarity protection | Yes |
| Input current | |
| from load voltage L+ (without load), max. | 160 mA |
| from backplane bus 5 V DC, max. | 85 mA |
| Power loss | |
| Power loss, typ. | 3 W |
| Digital outputs | |
| Number of digital outputs | 4 |
| Short-circuit protection | Yes; Electronic |
| Response threshold, typ. | Output current with short-circuit protection, min. 10 mA + 10 % |
| Load resistance range | |
| upper limit | 390 Ω; Two-wire connection |
| Output voltage | |
| Rated value (DC) | 24 V |
| Output current | |
| for signal "1" permissible range for 0 to 60 °C, max. | 10 mA; ±10 % |
| Switching frequency | |
| with resistive load, max. | 100 Hz |
| Cable length | |
| unshielded, max. | 200 m |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Diagnoses | |
| Diagnostic information readable | Yes |
| short-circuit | Yes |
| Diagnostics indication LED | |
| Group error SF (red) | Yes |
| Status indicator digital output (green) | Yes |
| Channel fault indicator F (red) | Yes |
| Ex(i) characteristics | |
| Module for Ex(i) protection | Yes |
| maximum values for connecting terminals for gas group IIC | |
| Uo (no-load voltage), max. | 25.2 V |
| Io (short-circuit current), max. | 70 mA |
| Po (power output), max. | 440 mW |
| Co (permissible external capacity), max. | 90 nF |
| Lo (permissible external inductivity), max. | 6.7 mH |
| Potential separation | |
| Potential separation digital outputs | |
| between the channels | Yes; 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area |
| between the channels, in groups of | 1 |
| between the channels and backplane bus | Yes; 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area |
| Between the channels and load voltage L+ | Yes; 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area |
| Standards, approvals, certificates | |
| Use in hazardous areas | |
| ATEX marking | [EEx ib] IIC |
| FM marking | AIS CL.1, DIV 1, GP A, B, C, D; CL.I, DIV 2, GP A, B, C, D T4 |
| Test number PTB | Ex-96.D.2093X |
| Ambient conditions | |
| Ambient temperature during operation | |
| max. | 60 °C |
| Connection method | |
| required front connector | 20-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights | |
| Weight, approx. | 230 g |
| Approvals / Certificates | |