6AG1326-1BK02-2AB0

Siemens 6AG1326-1BK02-2AB0

SIPLUS S7-300 SM 326F DI24 40-pole based on 6ES7326-1BK02-0AB0 with conformal coating, -25…+60 °C, 70° with forced convection, digital input F-DI 24x24 V DC fail-safe digital input for SIMATIC S7 F-systems with diagnostic alarm

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Product category
Digital modules
Manufacturer
SIEMENS
Product series
S7-300
General information
based on6ES7326-1BK02-0AB0
Supply voltage
Rated value (DC)24 V
Input current
from load voltage L+ (without load), max.450 mA
from backplane bus 5 V DC, max.100 mA
Encoder supply
Number of outputs4; Isolated
Output current
nominal400 mA
Power loss
Power loss, typ.10 W
Digital inputs
Number of digital inputs24
Number of simultaneously controllable inputs
all mounting positions
up to 40 °C, max.24
up to 60 °C, max.24; (at 24 V) or 18 (at 28.8 V)
Input voltage
Type of input voltageDC
Rated value (DC)24 V
for signal "0"-30 to +5 V
for signal "1"+11 to +30V
Input current
for signal "0", max. (permissible quiescent current)2 mA
for signal "1", typ.10 mA
Input delay (for rated value of input voltage)
for standard inputs
at "0" to "1", max.3.4 ms
at "1" to "0", max.3.4 ms
Cable length
shielded, max.200 m
unshielded, max.100 m
Encoder
Connectable encoders
2-wire sensorYes; if short-circuit test is deactivated
permissible quiescent current (2-wire sensor), max.2 mA
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Diagnoses
Diagnostic information readableYes
Diagnostics indication LED
Fail-safe operationYes
Group error SF (red)Yes
Potential separation
Potential separation digital inputs
between the channelsYes
between the channels, in groups of12
between the channels and backplane busYes
Isolation
Isolation tested with500 V DC/350 V AC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Highest safety class achievable in safety mode
acc. to DIN VDE 0801AK 6
acc. to EN 954Cat. 4
Performance level according to ISO 13849-1e
SIL acc. to IEC 61508SIL 3
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.60 °C; = Tmax; *+70 °C where forced convection with a minimum air velocity of 0.7 m/s through the modules and rated voltage of 24 V ±5 % are ensured. If in the course of maintenance or automatic diagnosis it is determined that the admissible specified parameters have been exceeded, the modules should be subjected to a proof test (function check) by the manufacturer.
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector40-pin
Dimensions
Width80 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.442 g
Approvals / Certificates