6AG1522-5HH00-7AB0

6AG1522-5HH00-7AB0

SIPLUS S7-1500 DQ 16x230VAC 2A RLY based on 6ES7522-5HH00-0AB0 with conformal coating, -40…+70 °C, start up -25 °C, digital output module relay 16 channels in groups of 2; 4 A per group; diagnostics.

Product category
Digital modules
Manufacturer
SIEMENS
Product series
S7-1500
General information
Product type designationDQ 16x 230 V AC/2 A ST (relay)
Firmware version
FW update possibleYes
based on6ES7522-5HH00-0AB0
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Prioritized startupYes
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
DQYes
DQ with energy-saving functionNo
PWMNo
OversamplingNo
MSOYes
Integrated operating cycle counterYes; FW V1.1.0 or higher
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.185 mA
Output voltage
Rated value (AC)230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC
Power
Power consumption from the backplane bus0.8 W
Power loss
Power loss, typ.5 W
Digital outputs
Type of digital outputRelays
Number of digital outputs16
Current-sinkingYes
Current-sourcingYes
Digital outputs, parameterizableYes
Short-circuit protectionNo
Controlling a digital inputYes
Size of motor starters according to NEMA, max.5
Switching capacity of the outputs
on lamp load, max.50 W (230 V AC), 5 W (24 V DC)
Output current
for signal "1" rated value2 A
for signal "1" permissible range, min.10 mA; 10 V
for signal "1" permissible range, max.2 A; thermal continuous current
for signal "0" residual current, max.0 A
Parallel switching of two outputs
for logic linksYes
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.1 Hz
with inductive load, max.0.5 Hz
on lamp load, max.1 Hz
Total current of the outputs
Current per channel, max.2 A; see additional description in the manual
Current per group, max.2 A; see additional description in the manual
Current per module, max.32 A; see additional description in the manual
Relay outputs
Number of relay outputs16
Rated supply voltage of relay coil L+ (DC)24 V
Current consumption of relays (coil current of all relays), typ.150 mA
external protection for relay outputsMiniature circuit breaker B10 / B16
Contact connection (internal)No
Number of operating cycles, max.see additional description in the manual
Switching capacity of contacts
with inductive load, max.2 A; see additional description in the manual
with resistive load, max.2 A; see additional description in the manual
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Maintenance interruptYes
Diagnoses
Monitoring the supply voltageYes
Wire breakNo
Short-circuitNo
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
MAINT LEDYes; Yellow LED
Monitoring of the supply voltage (PWR-LED)Yes; green LED
Channel status displayYes; green LED
for channel diagnosticsNo
for module diagnosticsYes; red LED
Potential separation
Potential separation channels
between the channelsNo
between the channels, in groups of2
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
between different circuits250 V AC between the channels and the supply voltage L+; 250 V AC between the channels and the backplane bus; 500 V AC between the channels
Isolation
Isolation tested withBetween channels: 3 100 V DC; between channels backplane bus: 3 100 V DC; between L+ and backplane bus: 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functionsNo
Suitable for safety-related tripping of standard modulesYes; From FS02
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]43.8 kg
global warming potential, (during production) [CO2 eq]9.5 kg
global warming potential, (during operation) [CO2 eq]34.5 kg
global warming potential, (after end of life cycle) [CO2 eq]-0.231 kg
Highest safety class achievable for safety-related tripping of standard modules
Performance level according to ISO 13849-1PL c
Category according to ISO 13849-1Cat. 2
SIL acc. to IEC 62061SIL 1
remark on safety-oriented shutdownhttps://support.industry.siemens.com/cs/de/en/view/39198632
Security
signed firmware updateNo
data integrityNo
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
horizontal installation, max.70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. 8 outputs (no adjacent points)
vertical installation, min.-40 °C; = Tmin; Startup @ -25 °C
vertical installation, max.40 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.350 g