SIMATIC S7-1500, analog output module AQ 4xU/I HF, 16-bit resolution accuracy 0.1%, 4 channels in groups of 1, common mode voltage: 30 V AC/60 V DC, diagnostics; substitute value, isochronous mode; the module supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015. delivery including infeed element, shielding bracket and shield terminal: front connector (screw terminals or push-in) to be ordered separately.

Product category
Analog modules
Manufacturer
SIEMENS
Product series
S7-1500
General information
Product type designationAQ 4xU/I HF
HW functional statusfrom FS01
Firmware versionV1.1.0
FW update possibleYes
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeYes
Prioritized startupYes
Output range scalableNo
Engineering with
STEP 7 TIA Portal configurable/integrated from versionV14 / -
STEP 7 configurable/integrated from versionV5.5 SP3 / -
PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
PROFINET from GSD version/GSD revisionV2.3 / -
Operating mode
OversamplingNo
MSOYes
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.160 mA
Power
Power consumption from the backplane bus0.95 W
Power loss
Power loss, typ.5 W
Analog outputs
Number of analog outputs4
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.24 mA
Current output, no-load voltage, max.22 V
Cycle time (all channels), min.125 µs; independent of number of activated channels
Analog output with oversamplingNo
Output ranges, voltage
0 to 10 VYes
1 V to 5 VYes
-5 V to +5 VNo
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mAYes
4 mA to 20 mAYes
Connection of actuators
for voltage output two-wire connectionYes
for voltage output four-wire connectionYes
for current output two-wire connectionYes
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ; 0.5 kOhm at 1 to 5 V
with voltage outputs, capacitive load, max.1 µF
with current outputs, max.750 Ω
with current outputs, inductive load, max.10 mH
Cable length
shielded, max.800 m; for current, 200 m for voltage
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Conversion time (per channel)125 µs; independent of number of activated channels
Settling time
for resistive load0.2 ms; see additional description in the manual
for capacitive load1.8 ms; see additional description in the manual
for inductive load2 ms; see additional description in the manual
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0.02 %
Linearity error (relative to output range), (+/-)0.015 %
Temperature error (relative to output range), (+/-)0.002 %/K
Crosstalk between the outputs, max.-100 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.005 %
note regarding accuracyat temperatures below 0 °C, the figures for operating error and temperature error are doubled
Operational error limit in overall temperature range
Voltage, relative to output range, (+/-)±10 V; 0 V to 10 V: ±0.12%; 1 V to 5 V: ±0.1%
Current, relative to output range, (+/-)±20 mA; 0 mA to 20 mA: ±0.2%; 4 mA to 20 mA: ±0.12%
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0.06 %
Current, relative to output range, (+/-)0.1 %
Isochronous mode
Execution and activation time (TCO), min.100 µs
Bus cycle time (TDP), min.250 µs
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnoses
Monitoring the supply voltageYes
Wire breakYes; Only for output type "current"
Short-circuitYes; Only for output type "voltage"
Overflow/UnderflowYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
Monitoring of the supply voltage (PWR-LED)Yes; green LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; red LED
Potential separation
Potential separation channels
between the channelsYes
between the channels, in groups of1
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
between different circuits60 V DC/30 V AC; insulation rated for 120 V AC basic insulation: between the channels and the supply voltage L+; between the channels and the backplane bus; between the channels
Isolation
Isolation tested with2 000 V DC between the channels and the supply voltage L+; 2 000 V DC between the channels and the backplane bus; 2 000 V DC between the channels; 707 V DC (type test) between the supply voltage L+ and the backplane bus
Standards, approvals, certificates
Siemens Eco Profile (SEP)Siemens EcoTech
Suitable for safety-related tripping of standard modulesYes; From FS03
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]37.6 kg
global warming potential, (during production) [CO2 eq]11.1 kg
global warming potential, (during operation) [CO2 eq]26.8 kg
global warming potential, (after end of life cycle) [CO2 eq]-0.364 kg
Highest safety class achievable for safety-related tripping of standard modules
Performance level according to ISO 13849-1PL d
Category according to ISO 13849-1Cat. 3
SIL acc. to IEC 62061SIL 2
remark on safety-oriented shutdownhttps://support.industry.siemens.com/cs/de/en/view/39198632
Security
signed firmware updateNo
securely removing dataNo
data integrityNo
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-25 °C; From FS02
horizontal installation, max.60 °C
vertical installation, min.-25 °C; From FS02
vertical installation, max.40 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Absolute humidity
dew point, min.-60 °C; suitable for dry room applications
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.300 g
Other
Note:please order front connectors (screw-in/push-in) separately
Approvals / Certificates