6AG1532-5HF00-7AB0

6AG1532-5HF00-7AB0

SIPLUS S7-1500 AQ 8xU/I HS based on 6ES7532-5HF00-0AB0 with conformal coating, -40…+70 °C, start up -25 °C, analog output module 16-bit resolution, accuracy 0.4%, 8 channels in groups of 8, diagnostics; substitute value 8 channels in 0.125 ms including infeed element, shielding bracket and shield terminal.

Product category
Analog modules
Manufacturer
SIEMENS
Product series
S7-1500
General information
Product type designationAQ 8xU/I HS
Firmware version
FW update possibleYes
based on6ES7532-5HF00-0AB0
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeYes
Prioritized startupNo
Output range scalableNo
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
OversamplingYes
MSOYes
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.320 mA; with 19.2 V supply
Power
Power consumption from the backplane bus1.15 W
Power loss
Power loss, typ.7 W
Analog outputs
Number of analog outputs8; > +60 °C max. 4x ±10 V permissible
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.45 mA
Current output, no-load voltage, max.20 V
Cycle time (all channels), min.125 µs; independent of number of activated channels
Output ranges, voltage
0 to 10 VYes
1 V to 5 VYes
-5 V to +5 VNo
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mAYes
4 mA to 20 mAYes
Connection of actuators
for voltage output two-wire connectionYes
for voltage output four-wire connectionYes
for current output two-wire connectionYes
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ
with voltage outputs, capacitive load, max.100 nF
with current outputs, max.500 Ω
with current outputs, inductive load, max.1 mH
Cable length
shielded, max.200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Conversion time (per channel)50 µs; independent of number of activated channels
Settling time
for resistive load30 µs; see additional description in the manual
for capacitive load100 µs; see additional description in the manual
for inductive load100 µs; see additional description in the manual
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0.02 %
Linearity error (relative to output range), (+/-)0.15 %
Temperature error (relative to output range), (+/-)0.002 %/K
Crosstalk between the outputs, max.-100 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.05 %
note regarding accuracyat temperatures below 0 °C, the figures for operating error and temperature error are doubled
Operational error limit in overall temperature range
Voltage, relative to output range, (+/-)0.4 %
Current, relative to output range, (+/-)0.4 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0.2 %
Current, relative to output range, (+/-)0.2 %
Isochronous mode
Execution and activation time (TCO), min.100 µs
Bus cycle time (TDP), min.250 µs
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnoses
Monitoring the supply voltageYes
Wire breakYes; Only for output type "current"
Short-circuitYes; Only for output type "voltage"
Overflow/UnderflowYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
Monitoring of the supply voltage (PWR-LED)Yes; green LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; red LED
Potential separation
Potential separation channels
between the channelsNo
between the channels, in groups of8
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
between S- and MANA (UCM)8 V DC
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for safety-related tripping of standard modulesYes; from FS04
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]37.6 kg
global warming potential, (during production) [CO2 eq]11.1 kg
global warming potential, (during operation) [CO2 eq]26.8 kg
global warming potential, (after end of life cycle) [CO2 eq]-0.364 kg
Highest safety class achievable for safety-related tripping of standard modules
Performance level according to ISO 13849-1PL d
Category according to ISO 13849-1Cat. 3
SIL acc. to IEC 62061SIL 2
remark on safety-oriented shutdownhttps://support.industry.siemens.com/cs/de/en/view/39198632
Security
signed firmware updateNo
data integrityNo
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
horizontal installation, max.70 °C; = Tmax; > +60 °C max. 4x ±10 V permissible
vertical installation, min.-40 °C; = Tmin; Startup @ -25 °C
vertical installation, max.40 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.325 g
Approvals / Certificates