7MH4960-2AA01

7MH4960-2AA01

SIWAREX WP231 calibratable weighing electronic (1 channel) for strain gauge load cells / full bridges (1-4 mV/V) for SIMATIC S7-1200 or stand alone, RS485 and Ethernet-Interface, onboard I/O: 4 DI / 4 DO, 1 AO (0/4...20mA), attention: for calibratable applications please follow the local laws applying in the country of verification! Detailed load cell diagnostics possible with digital junction box SIWAREX DB (7MH5001-0AD20 or 7MH5001-0AD01).

Product category
Technology modules
Manufacturer
SIEMENS
Product series
S7-1200
General information
Product type designationSIWAREX WP231
Firmware version
FW update possibleYes
Installation type/mounting
Rail mountingYes; Standard - DIN rail
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Short-circuit protectionYes
Reverse polarity protectionYes
Input current
Current consumption, max.200 mA
from backplane bus 5 V DC, typ.3 mA
Power loss
Power loss, typ.4.5 W
Digital inputs
Number of digital inputs4
Digital inputs, parameterizableYes
Input voltage
Type of input voltageDC
Rated value (DC)24 V
for signal "0"5 V DC at 1 mA
for signal "1"15 V DC at 2.5 mA
Digital outputs
Number of digital outputs4
Short-circuit protectionYes
Switching capacity of the outputs
with resistive load, max.0.5 A
Output voltage
Type of output voltageDC
Rated value (DC)24 V
Output delay with resistive load
"0" to "1", max.25 µs
"1" to "0", max.150 µs
Total current of the outputs
Current per channel, max.0.5 A
Current per module, max.4 A
Cable length
shielded, max.500 m
unshielded, max.150 m
Analog outputs
Number of analog outputs1
Output ranges, current
0 to 20 mAYes
4 mA to 20 mAYes
Load impedance (in rated range of output)
with current outputs, max.600 Ω
Cable length
shielded, max.100 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Encoder
Connection of signal encoders
For strain gauges (full bridges) with 4-conductor connectionYes
For strain gauges (full bridges) with 6-conductor connectionYes
Resistance of full bridge, min.40 Ω; when using SIWAREX IS: 50 ohm for 7MH4710-5BA; 105 ohm when using 7MH4710-5CA
Resistance of full bridge, max.4 100 Ω
Interfaces
Number of RS 485 interfaces1; SIWATOOL V7 or SIWAREX DB or SIEBERT remote display
1. Interface
Interface types
RS 485Yes
2. Interface
Interface types
RJ 45 (Ethernet)Yes
Number of ports1
Interface types
RS 485
Transmission rate, max.115.2 bit/s
Cable length, max.1 000 m; ≤ 115 kbps, shielded cable
Interrupts/diagnostics/status information
Diagnostics functionYes; Diagnostic alarm
Substitute values connectableYes
Alarms
Diagnostic alarmYes; Parameterizable
Hardware interruptYes; Parameterizable
Diagnoses
Monitoring the supply voltageYes
Wire breakYes
Short-circuitYes
Diagnostics indication LED
DIAG LEDYes
for status of the inputsYes
for status of the outputsYes
for maintenanceYes
Integrated Functions
CounterNo
Load cell
Non-automatic weighing instrumentNAWI
Sampling rate100 Hz
Resolution of input signal±1 000 000 parts pro mV/V
Common mode voltage, min.0 V
Common mode voltage, max.5 V
Cable length, max.500 m; when using the SIWAREX 7MH4702-8AG cable
Measuring functions
Measuring range
-1 mV/V to +1 mV/VYes
-2 mV/V to +2 mV/VYes
-4 mV/V to +4 mV/VYes
Potential separation
Potential separation digital inputs
between the channels and backplane busYes
Potential separation digital outputs
between the channels and backplane busYes
Potential separation analog outputs
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with707 V DC (type test)
Degree and class of protection
IP degree of protectionIP20
Standards, approvals, certificates
CE markYes; CE marking / EC Declaration of Conformity
cULusYes; UL 508 (Industrial Control Equipment), CSA C22.2 No. 142 (Process Control Equipment)
FM approvalYes
RCM (formerly C-TICK)Yes
KC approvalYes
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]174.83 kg
global warming potential, (during production) [CO2 eq]32.12 kg
global warming potential, (during operation) [CO2 eq]140.99 kg
global warming potential, (after end of life cycle) [CO2 eq]1.72 kg
Ambient conditions
Free fall
Fall height, max.1 m; five times, in product package
Ambient temperature during operation
horizontal installation, min.-10 °C
horizontal installation, max.40 °C
vertical installation, min.-10 °C
vertical installation, max.60 °C
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Air pressure acc. to IEC 60068-2-13
Operation, min.795 hPa
Operation, max.1 080 hPa
Storage/transport, min.660 hPa
Storage/transport, max.1 080 hPa
Altitude during operation relating to sea level
Ambient air temperature-barometric pressure-altitude​1 080 ... 795 hPa (-1 000 ... 5 000 m above sea level)
Vibrations
Vibration resistance during operation acc. to IEC 60068-2-65  ...  8.4 Hz / 3.5 mm, 8.4  ...  150 Hz / 1 g; For wall mounting: 9  ...  29 Hz / 1.5 mm, 29  ...  200 Hz / 5 g
Operation, tested according to IEC 60068-2-6Yes
Shock testing
tested according to IEC 60068-2-27Yes; 150 m/s², 11 ms
Mechanics/material
Enclosure material (front)plastic
PlasticYes
Dimensions
Width70 mm
Height100 mm
Depth75 mm
Weights
Weight, approx.280 g
Approvals / Certificates