6ES7223-1BH32-0XB0

6ES7223-1BH32-0XB0

SIMATIC S7-1200, Digital I/O SM 1223, 8 DI/8 DO, 8 DI 24 V DC, Sink/Source, 8 DO, transistor 0.5 A.

Product category
Signal modules
Manufacturer
SIEMENS
Product series
S7-1200
General information
Product type designationSM 1223, DI 8x24 V DC, DQ 8x24 V DC
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
from backplane bus 5 V DC, max.145 mA
Digital inputs
from load voltage L+ (without load), max.4 mA; per channel
Output voltage
Power supply to the transmitters
presentYes
Power loss
Power loss, typ.2.5 W
Digital inputs
Number of digital inputs8
in groups of2
Input characteristic curve in accordance with IEC 61131, type 1Yes
Number of simultaneously controllable inputs
all mounting positions
up to 40 °C, max.8
horizontal installation
up to 40 °C, max.8
up to 50 °C, max.8
vertical installation
up to 40 °C, max.8
Input voltage
Rated value (DC)24 V
for signal "0"5 V DC at 1 mA
for signal "1"15 V DC at 2.5 mA
Input current
for signal "0", max. (permissible quiescent current)1 mA
for signal "1", min.2.5 mA
for signal "1", typ.4 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizableYes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four
for interrupt inputs
ParameterizableYes
Cable length
shielded, max.500 m
unshielded, max.300 m
Digital outputs
Number of digital outputs8
in groups of1
Short-circuit protectionNo; to be provided externally
Limitation of inductive shutdown voltage toL+ (-48 V)
Switching capacity of the outputs
with resistive load, max.0.5 A
on lamp load, max.5 W
Output voltage
Rated value (DC)24 V
for signal "0", max.0.1 V; with 10 kOhm load
for signal "1", min.20 V DC
Output current
for signal "1" rated value0.5 A
for signal "1" permissible range, max.0.5 A
for signal "0" residual current, max.10 µA
Output delay with resistive load
"0" to "1", max.50 µs
"1" to "0", max.200 µs
Total current of the outputs (per group)
horizontal installation
up to 50 °C, max.4 A; Current per mass
Cable length
shielded, max.500 m
unshielded, max.150 m
Interrupts/diagnostics/status information
Alarms
Diagnostic alarmYes
Diagnostics indication LED
for status of the inputsYes
for status of the outputsYes
Potential separation
Potential separation digital inputs
between the channels, in groups of2
Potential separation digital outputs
between the channels, in groups of1
between the channels and backplane bus500 V AC
Degree and class of protection
IP degree of protectionIP20
Standards, approvals, certificates
CE markYes
CSA approvalYes
UL approvalYes
cULusYes
FM approvalYes
RCM (formerly C-TICK)Yes
KC approvalYes
Marine approvalYes
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]123 kg
global warming potential, (during production) [CO2 eq]12.1 kg
global warming potential, (during operation) [CO2 eq]111 kg
global warming potential, (after end of life cycle) [CO2 eq]-0.434 kg
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.-20 °C
max.60 °C
horizontal installation, min.-20 °C
horizontal installation, max.60 °C
vertical installation, min.-20 °C
vertical installation, max.50 °C
permissible temperature change5°C to 55°C, 3°C / minute
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Air pressure acc. to IEC 60068-2-13
Storage/transport, min.660 hPa
Storage/transport, max.1 080 hPa
Relative humidity
Operation at 25 ℃ without condensation, max.95 %
Connection method
required front connectorYes
Mechanics/material
Enclosure material (front)
PlasticYes
Dimensions
Width45 mm
Height100 mm
Depth75 mm
Weights
Weight, approx.210 g
Approvals / Certificates