6AG1221-1BH32-4XB0

6AG1221-1BH32-4XB0

SIPLUS S7-1200 SM 1221 16DI, based on 6ES7221-1BH32-0XB0 with conformal coating, -20…+60 °C, 16 DI, 24 V DC, sink/source.

Product category
Signal modules
Manufacturer
SIEMENS
Product series
S7-1200
General information
Product type designationSM 1221, DI 16x24 V DC
based on6ES7221-1BH32-0XB0
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
from backplane bus 5 V DC, max.130 mA
Digital inputs
from load voltage L+ (without load), max.4 mA; per channel
Output voltage
Power supply to the transmitters
presentYes
Power loss
Power loss, typ.2.5 W
Digital inputs
Number of digital inputs16
in groups of4
Input characteristic curve in accordance with IEC 61131, type 1Yes
Number of simultaneously controllable inputs
all mounting positions
up to 40 °C, max.16
horizontal installation
up to 40 °C, max.16
up to 50 °C, max.16
vertical installation
up to 40 °C, max.16
Input voltage
Rated value (DC)24 V
for signal "0"5 V DC at 1 mA
for signal "1"15 V DC at 2.5 mA
Input current
for signal "0", max. (permissible quiescent current)1 mA
for signal "1", min.2.5 mA
for signal "1", typ.4 mA
Input delay (for rated value of input voltage)
for standard inputs
ParameterizableYes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four
for interrupt inputs
ParameterizableYes
Cable length
shielded, max.500 m
unshielded, max.300 m
Interrupts/diagnostics/status information
Alarms
Diagnostic alarmYes
Diagnostics indication LED
for status of the inputsYes
Potential separation
Potential separation digital inputs
between the channels, in groups of4
Degree and class of protection
IP degree of protectionIP20
Standards, approvals, certificates
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]123 kg
global warming potential, (during production) [CO2 eq]12.1 kg
global warming potential, (during operation) [CO2 eq]111 kg
global warming potential, (after end of life cycle) [CO2 eq]-0.434 kg
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.-20 °C; = Tmin (incl. condensation/frost); start-up @ 0 °C
max.60 °C; = Tmax
At cold restart, min.0 °C
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Connection method
required front connectorYes
Mechanics/material
Enclosure material (front)
PlasticYes
Dimensions
Width45 mm
Height100 mm
Depth75 mm
Weights
Weight, approx.210 g
Approvals / Certificates