6AG1231-5PA30-5XB0

6AG1231-5PA30-5XB0

SIPLUS S7-1200 SB 1231 1AI RTD based on 6ES7231-5PA30-0XB0 with conformal coating, -40…+60 °C, start up -25 °C, SIPLUS S7-1200, analog input, SB 1231RTD, 1 AI RTD, Pt100 and Pt1000.

Product category
Signal boards
Manufacturer
SIEMENS
Product series
S7-1200
General information
Product type designationSB 1231, AI 1x16 bit RTD
based on6ES7231-5PA30-0XB0
Supply voltage
Rated value (DC)24 V
Input current
Current consumption, typ.5 mA
from backplane bus 5 V DC, typ.20 mA
Power loss
Power loss, typ.0.5 W
Analog inputs
Number of analog inputs1; Resistance thermometer
permissible input voltage for current input (destruction limit), max.±35 V
Technical unit for temperature measurement adjustableDegrees Celsius/degrees Fahrenheit
Input ranges
VoltageYes
CurrentNo
ThermocoupleNo
Resistance thermometerYes; Platinum (Pt)
ResistanceYes; 150 Ω, 300 Ω, 600 Ω
Input ranges (rated values), voltages
-80 mV to +80 mV
Input resistance (-80 mV to +80 mV)>= 10 MOhm
Input ranges (rated values), resistance thermometer
Pt 100Yes
Input resistance (Pt 100)100 Ω
Pt 1000Yes
Input resistance (Pt 1000)1 000 Ω
Pt 200Yes
Input resistance (Pt 200)200 Ω
Pt 500Yes
Input resistance (Pt 500)500 Ω
Input ranges (rated values), resistors
0 to 150 ohmsYes
0 to 300 ohmsYes
0 to 600 ohmsYes
Thermocouple (TC)
Temperature compensation
ParameterizableNo
Analog outputs
Number of analog outputs0
Cable length
shielded, max.100 m; shielded, twisted pair
Analog value generation for the inputs
Measurement principleintegrating
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.15 bit; + sign
Integration time, parameterizableNo
Interference voltage suppression for interference frequency f1 in Hz85 dB at 10 / 50 / 60 / 400 Hz
Errors/accuracies
Temperature error (relative to input range), (+/-)25 °C ±0.1%, up to 55 °C ±0.25% total measurement range
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.05 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Common mode interference, min.120 dB
Interrupts/diagnostics/status information
AlarmsYes
Diagnostics functionYes; Can be read out
Alarms
Diagnostic alarmYes
Diagnoses
Wire breakYes
Diagnostics indication LED
for status of the inputsYes
for maintenanceYes
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
max.60 °C; = Tmax
vertical installation, min.-40 °C; = Tmin; Startup @ -25 °C
vertical installation, max.50 °C; = Tmax
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Connection method
required front connectorYes
Mechanics/material
Enclosure material (front)
PlasticYes
Dimensions
Width38 mm
Height62 mm
Depth21 mm
Weights
Weight, approx.35 g
Approvals / Certificates