6AG1332-1SH71-4AA0

6AG1332-1SH71-4AA0

SIPLUS S7-1200 PM 1207 based on 6EP1332-1SH71 with conformal coating, 0…+60 °C, stabilized power supply input: 120/230 V AC output: 24 V DC/2.5 A.

Product category
Power supplies
Manufacturer
SIEMENS
Product series
S7-1200
General information
Technical Product Detail Pagehttps://i.siemens.com/1P6AG1332-1SH71-4AA0
product brand nameSIPLUS
product type designationPM 1207
product designationS7-1200 Power Module
type of current supply24 V/2.5 A
manufacturer's article number of the basic version used for SIPLUS product versions6EP1332-1SH71
input
type of the power supply network1-phase AC
phase number1
voltage curve at inputAC
supply voltage at ACAutomatic range selection
supply voltage120 V/230 V
input voltage 1 at AC85 ... 132 V
input voltage 2 at AC176 ... 264 V
supply voltage
at 50 Hz230 V
at 60 Hz120 V
line frequency50/60 Hz
line frequency47 ... 63 Hz
wide range inputNo
overvoltage overload capability2.3 × Vin rated, 1.3 ms
buffering time for rated value of the output current in the event of power failure minimum20 ms
operating condition of the mains bufferingat Vin = 93/187 V
input current
at rated input voltage 120 V1.2 A
at rated input voltage 230 V0.67 A
current limitation of inrush current at 25 °C maximum13 A
duration of inrush current limiting at 25 °C
maximum3 ms
I2t value maximum0.5 A²·s
fuse protection typeT 3,15 A/250 V (not accessible)
fuse protection type in the feederRecommended miniature circuit breaker: 16 A characteristic B or 10 A characteristic C
output
voltage curve at outputControlled, isolated DC voltage
product function output voltage controlledYes
product function output voltage stabilizedYes
output voltage at DC rated value24 V
output voltage
at output 1 at DC rated value24 V
output voltage
at output 1 at DC24 V
output voltage adjustableNo; -
relative overall tolerance of the voltage3 %
relative control precision of the output voltage
on slow fluctuation of input voltage0.1 %
on slow fluctuation of ohm loading0.2 %
residual ripple
maximum150 mV
voltage peak
maximum240 mV
display version for normal operationGreen LED for 24 V OK
behavior of the output voltage when switching onNo overshoot of Vout (soft start)
response delay maximum6 s; 2 s at 230 V, 6 s at 120 V
voltage increase time of the output voltage
typical10 ms
output current
rated value2.5 A
rated range0 ... 2.5 A
supplied active power typical60 W
short-term overload current
on short-circuiting during the start-up typical6 A
at short-circuit during operation typical6 A
duration of overloading capability for excess current
on short-circuiting during the start-up100 ms
at short-circuit during operation100 ms
bridging of equipmentYes
number of parallel-switched equipment resources for increasing the power2
efficiency
efficiency in percent83 %
power loss [W]
at rated output voltage for rated value of the output current typical12 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical0.3 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical3 %
setting time
load step 50 to 100% typical5 ms
load step 100 to 50% typical5 ms
setting time
maximum5 ms
protection and monitoring
design of the overvoltage protection< 33 V
property of the output short-circuit proofYes
design of short-circuit protectionConstant current characteristic
typical2.65 A
enduring short circuit current RMS value
typical2.7 A
safety
galvanic isolation between input and outputYes
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass I
leakage current
maximum3.5 mA
protection class IPIP20
EMC
standard
for emitted interferenceEN 55022 Class B
for mains harmonics limitationnot applicable
for interference immunityEN 61000-6-2
standards, specifications, approvals
certificate of suitability
CE markingYes
UKCA markingYes
MTBF at 40 °C1 492 537 h
ambient conditions
ambient temperature
in horizontal mounting position during operation0 ... 60 °C; with natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
installation altitude at height above sea level maximum6 000 m
ambient condition relating to ambient temperature - air pressure - installation altitudeIn case of operation at altitudes of 2000 - 6000 m above sea level: Output power derating of -7.5 %/1000 m or reduction of the ambient temperature by 5 K/1000 m
relative humidity with condensation according to IEC 60068-2-38 maximum100 %; RH incl. condensation/frost (no commissioning if condensation is present), horizontal installation
chemical resistance to commercially available cooling lubricantsYes; incl. diesel and oil droplets in the air
resistance to biologically active substances conformity according to EN 60721-3-3Yes; Class 3B2 mold, fungal, sponge spores (except fauna); class 3B3 upon request
resistance to chemically active substances conformity according to EN 60721-3-3Yes; Class 3C4 (RH < 75%) incl. salt spray acc. to EN 60068-2-52 (severity level 3)
resistance to mechanically active substances conformity according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust
resistance to biologically active substances conformity according to EN 60721-3-6Yes; Class 6B2 mold, fungal, sponge spores (except fauna)
resistance to chemically active substances conformity according to EN 60721-3-6Yes; Class 6C3 (RH < 75%) incl. salt spray acc. to EN 60068-2-52 (severity level 3)
resistance to mechanically active substances conformity according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust
coating for equipped printed circuit board according to EN 61086Yes; Class 2 for high availability
type of coating protection against pollution according to EN 60664-3Yes; Type 1 protection
type of test of the coating according to MIL-I-46058CYes; Discoloration of the coating during service life possible
product conformity of the coating Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal Coating, Class A
connection method
type of electrical connectionscrew terminal
at inputL, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
at outputL+, M: 2 screw terminals each for 0.5 ... 2.5 mm²
for auxiliary contacts-
mechanical data
width × height × depth of the enclosure70 × 100 × 75 mm
installation width × mounting height70 mm × 140 mm
required spacing
top20 mm
bottom20 mm
left0 mm
right0 mm
fastening methodSnaps onto DIN rail EN 60715 35x7.5/15, wall mounting
DIN-rail mountingYes
S7 rail mountingNo
wall mountingYes
housing can be lined upYes
net weight0.3 kg
further information internet links
internet link
to website: Industry Mallhttps://mall.industry.siemens.com
to website: Industry Online Supporthttps://support.industry.siemens.com
additional information
other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)
security information
security informationSiemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under https://www.siemens.com/cert. (V4.7)
Approvals Certificates