6AV3688-3AF37-0AX0

6AV3688-3AF37-0AX0

SIMATIC HMI KP8F PN, Key Panel, 8 Kurzhubtaster mit mehrfarbigen LEDs, PROFINET-Schnittstellen mit PROFIsafe; 8 DI/DO und 2 sicherheitsgerichtete DI-Pins, 24 V DC durchschleifbar, parametrierbar ab STEP 7 V5.5.

Produktkategorie
Thin Clients
Hersteller
SIEMENS
Produktreihe
SIMATIC HMI
General information
Product type designationKP8F PN
Control elements
With parameterizable keysYes
Keyboard
Membrane keyboard
user-definable label membrane keysYes
Function keys
Number of function keys8
Short-stroke keys
Number of short-stroke keys8
Expansions for operator control of the process
DP direct LEDs (LEDs as S7 output I/O)8; Adjustable brightness
Number of color modes for LED5; red, green, blue, yellow, white
Direct keys (keys as S7 input I/O)8
Installation type/mounting
Mounting typeMounting clip
Mounting positionvertical
Rack mountingNo
Front mountingYes; Compatible with Extension Units dimensions
Rail mountingNo
Wall mounting/direct mountingNo
Mounting in portrait format possibleYes
Mounting in landscape format possibleYes
maximum permissible angle of inclination without external ventilation30°; To the front/rear
Number of slots for command devices and signaling units0
Supply voltage
Type of supply voltageDC
Rated value (DC)24 V; 24 V can be looped through connector, interrupted when pulled
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
Current consumption (rated value)0.3 A
Digital inputs
Number of digital inputs8; total inputs and outputs max. 8 and 2x SIL 2 or 1x SIL 3
Input voltage
Rated value (DC)24 V
Digital outputs
Number of digital outputs8; Max. 8 inputs and outputs (total)
Short-circuit protectionYes
Switching capacity of the outputs
with resistive load, max.100 mA
Output voltage
Rated value (DC)24 V; Non-isolated
Total current of the outputs
Current per channel, max.100 mA
Current per group, max.800 mA
Interfaces
Number of industrial Ethernet interfaces2; For the construction of lines and rings without external switch
Number of PROFINET interfaces2; Incl. switch
Industrial Ethernet
Industrial Ethernet status LED2; Per port
Number of ports of the integrated switch2; Per port
Protocols
PROFINETYes; also 3rd party PLC
Supports protocol for PROFINET IOYes
PROFINET CBANo
IRTYes
PROFIsafeYes; 1x SIL 3 (two-channel) or 2x SIL 2 (single-channel) emergency stop sensors
PROFIBUSNo
EtherNet/IPNo
MPINo
AS-InterfaceNo
EIB/KNXNo
Protocols (Ethernet)
TCP/IPNo
Redundancy mode
Media redundancy
MRPYes
Further protocols
AS-Interface Safety at WorkNo
CANNo
Data-HighwayNo
DeviceNetNo
DeviceNet SafetyNo
Foundation FieldbusNo
INTERBUSNo
INTERBUS-SafetyNo
Local Operating NetworkNo
MODBUSNo
SafetyBUS pNo
SERCOSNo
SUCOnetNo
other bus systemsNo
Test commissioning functions
Illuminant testYes; During switch on
Key and signal lamp testYes; automatically when switching on
EMC
Emission of radio interference acc. to EN 55 011
Limit class A, for use in industrial areasYes; Group 1, measured at a distance of 10 m
Limit class B, for use in residential areasNo
Degree and class of protection
IP (at the front)IP65
IP (rear)IP20
NEMA (front)
Enclosure Type 4 at the frontNo
Enclosure Type 4x at the frontYes; Incl. NEMA12
Standards, approvals, certificates
CE markYes
cULusYes
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
CCCNo; not necessary
Suitable for safety functionsYes
Use in hazardous areas
ATEX Zone 2Yes
ATEX Zone 22Yes
cULus Class I Zone 1No
cULus Class I Zone 2, Division 2Yes
FM Class I Division 2Yes
Marine approval
Germanischer Lloyd (GL)No
American Bureau of Shipping (ABS)No
Bureau Veritas (BV)No
Det Norske Veritas (DNV)No
Lloyds Register of Shipping (LRS)No
Nippon Kaiji Kyokai (Class NK)No
Polski Rejestr Statkow (PRS)No
Ambient conditions
Ambient temperature during operation
min.0 °C
max.55 °C
Operation (vertical installation)
For vertical installation, min.0 °C
For vertical installation, max.55 °C
Operation (max. tilt angle)
At maximum tilt angle, min.0 °C
At maximum tilt angle, max.45 °C
Operation (vertical installation, portrait format)
For vertical installation, min.0 °C
For vertical installation, max.55 °C
Operation (max. tilt angle, portrait format)
At maximum tilt angle, min.0 °C
At maximum tilt angle, max.45 °C
Ambient temperature during storage/transportation
min.-20 °C
max.60 °C
Relative humidity
Operation, max.95 %; no condensation
Configuration
Configuration software
STEP 7 Basic (TIA Portal)Yes
STEP 7 Professional (TIA Portal)Yes
Functionality under WinCC (TIA Portal)
Process coupling
S7-1200Yes; with ET 200pro CPU and ET 200S CPU
S7-1500Yes
S7-200No
S7-300/400Yes; with F-CPU: STEP 7 V11 SP1 (or higher) and Safety V11 (or higher) or SIMATIC STEP 7 Basic V11 (or higher)
LOGO!No
WinACYes
SINUMERIKNo
SIMOTIONNo
Allen Bradley (EtherNet/IP)No
Allen Bradley (DF1)No
Mitsubishi (MC TCP/IP)No
Mitsubishi (FX)No
OMRON (FINS TCP)No
OMRON (Host Link)No
Modicon (Modbus TCP/IP)No
Modicon (Modbus RTU)No
Mechanics/material
Enclosure material (front)
PlasticYes
AluminumNo
Stainless steelNo
Service life
Short-stroke keys (in switching cycles)1 500 000
LEDs (ON period)100 %
Dimensions
Width of the housing front98 mm
Height of housing front155 mm
Mounting cutout, width67.7 mm; Max. thickness of mounting plate 2 - 6 mm
Mounting cutout, height129.7 mm
mounting depth49 mm; Incl. angled SIMATIC Ethernet connector
Weights
Weight (without packaging)280 g