6AG1331-7NF00-2AB0
SIPLUS S7-300 SM 331 40-pole based on 6ES7331-7NF00-0AB0 with conformal coating, -25…+70 °C, analog input isolated 8 AI; +/-5/10V, 1-5 V, +/-20 mA, 0/4 to 20 mA, 16 bit (55 ms), single-point grounding (50 V common)
Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.
Produktkategorie
AnalogmoduleHersteller
SIEMENSProduktreihe
S7-300| General information | |
|---|---|
| based on | 6ES7331-7NF00-0AB0 |
| Product function | |
| Isochronous mode | No |
| Input current | |
| from backplane bus 5 V DC, max. | 130 mA |
| Power loss | |
| Power loss, typ. | 0.6 W |
| Analog inputs | |
| Number of analog inputs | 8 |
| permissible input voltage for voltage input (destruction limit), max. | 50 V; Permanent |
| permissible input current for current input (destruction limit), max. | 32 mA |
| Input ranges | |
| Voltage | Yes |
| Current | Yes |
| Thermocouple | No |
| Resistance thermometer | No |
| Resistance | No |
| Input ranges (rated values), voltages | |
| 0 to +10 V | No |
| 1 V to 5 V | Yes |
| Input resistance (1 V to 5 V) | 2 MΩ |
| 1 V to 10 V | No |
| -1 V to +1 V | No |
| -10 V to +10 V | Yes |
| Input resistance (-10 V to +10 V) | 2 MΩ |
| -2.5 V to +2.5 V | No |
| -250 mV to +250 mV | No |
| -5 V to +5 V | Yes |
| Input resistance (-5 V to +5 V) | 2 MΩ |
| -50 mV to +50 mV | No |
| -500 mV to +500 mV | No |
| -80 mV to +80 mV | No |
| Input ranges (rated values), currents | |
| 0 to 20 mA | Yes |
| Input resistance (0 to 20 mA) | 250 Ω |
| -20 mA to +20 mA | Yes |
| Input resistance (-20 mA to +20 mA) | 250 Ω |
| -3.2 mA to +3.2 mA | No |
| 4 mA to 20 mA | Yes |
| Input resistance (4 mA to 20 mA) | 250 Ω |
| Input ranges (rated values), thermocouples | |
| type B | No |
| type C | No |
| Type E | No |
| Type J | No |
| Type K | No |
| Type L | No |
| Type N | No |
| Type R | No |
| Type S | No |
| Type T | No |
| Type U | No |
| Type TXK/TXK(L) to GOST | No |
| Input ranges (rated values), resistance thermometer | |
| Cu 10 | No |
| Ni 100 | No |
| Ni 1000 | No |
| LG-Ni 1000 | No |
| Ni 120 | No |
| Ni 200 | No |
| Ni 500 | No |
| Pt 100 | No |
| Pt 1000 | No |
| Pt 200 | No |
| Pt 500 | No |
| Input ranges (rated values), resistors | |
| 0 to 150 ohms | No |
| 0 to 300 ohms | No |
| 0 to 600 ohms | No |
| 0 to 6000 ohms | No |
| Cable length | |
| shielded, max. | 200 m |
| Analog value generation for the inputs | |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 16 bit; Unipolar: 15/15/15/15 bit; bipolar: 15 bit + sign/15 bit + sign/15 bit + sign/15 bit + sign |
| Integration time, parameterizable | Yes; 10/ 16.67/ 20/ 100 ms |
| Interference voltage suppression for interference frequency f1 in Hz | 400 / 60 / 50 / 10 Hz |
| Encoder | |
| Connection of signal encoders | |
| for voltage measurement | Yes |
| for current measurement as 2-wire transducer | Yes; with external transmitter; possible with separate supply for transmitter |
| for current measurement as 4-wire transducer | Yes |
| Errors/accuracies | |
| Operational error limit in overall temperature range | |
| Voltage, relative to input range, (+/-) | 0.1 %; @ Ucm = 0 V; @ Ucm = ±50 V: ±0.7 % - @ 0 ... +60 °C; ±0.5 % @ Ucm = 0 V; @ Ucm = ±50 V: ±0.9 % - @ -25 ... +70 °C; |
| Current, relative to input range, (+/-) | 0.3 %; @ Ucm = 0 V; @ Ucm = ±50 V: ±0.4 % @ 0 ... +60 °C; ±0.5% @ Ucm = 0 V; @ Ucm = ±50 V: ±0.6% @ -25 ... +70 °C |
| Basic error limit (operational limit at 25 °C) | |
| Voltage, relative to input range, (+/-) | 0.05 % |
| Current, relative to input range, (+/-) | 0.05 % |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes; Parameterizable |
| Alarms | |
| Diagnostic alarm | Yes; Parameterizable |
| Limit value alarm | Yes; Parameterizable, channels 0 and 2 |
| Diagnoses | |
| Diagnostic information readable | Yes |
| Diagnostics indication LED | |
| Group error SF (red) | Yes |
| Potential separation | |
| Potential separation analog inputs | |
| between the channels | No |
| between the channels, in groups of | 2 |
| between the channels and backplane bus | Yes |
| Isolation | |
| Isolation tested with | 500 V DC |
| Standards, approvals, certificates | |
| CE mark | Yes |
| UL approval | Yes; File E239877 |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| EAC (formerly Gost-R) | Yes |
| Railway application | |
| EN 50155 | Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B, EN 50155:2007 (see SIOS entry 109755985) |
| Ambient conditions | |
| Ambient temperature during operation | |
| min. | -25 °C; = Tmin |
| max. | 70 °C; = Tmax; for use on railway vehicles according to EN 50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/UL hazardous use applies |
| Ambient temperature during storage/transportation | |
| min. | -40 °C |
| max. | 70 °C |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m |
| Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
| Relative humidity | |
| With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Resistance | |
| Use in stationary industrial systems | |
| to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
| Use on land craft, rail vehicles and special-purpose vehicles | |
| to biologically active substances according to EN 60721-3-5 | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request |
| to chemically active substances according to EN 60721-3-5 | Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 50155 (ST2); * |
| to mechanically active substances according to EN 60721-3-5 | Yes; Class 5S3 incl. sand, dust; * |
| Use on ships/at sea | |
| to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
| to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
| Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
| Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| Connection method | |
| required front connector | 40-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 117 mm |
| Weights | |
| Weight, approx. | 272 g |
| Approvals / Certificates | |