6AG1505-0RA00-7AB0

6AG1505-0RA00-7AB0

SIPLUS S7-1500 PS 1505 60W 24/48/60V DC на основі 6ES7505-0RA00-0AB0 із захисним лакуванням, -40…+70 °C, запуск за температури -25 °C, системне джерело живлення, яке подає робочу напругу на внутрішню шину S7-1500.

Категорія товару
Блоки живлення
Виробник
SIEMENS
Серія продуктів
S7-1500
General information
Product type designationPS 60 W 24/48/60 V DC
based on6ES7505-0RA00-0AB0
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Supply voltage
Rated value (DC)24 V / 48 V / 60 V
permissible range, lower limit (DC)19.2 V; Static 19.2 V, dynamic 18.5 V
permissible range, upper limit (DC)72 V; Static 72 V, dynamic 75.5 V
Reverse polarity protectionYes
Short-circuit protectionYes
Mains buffering
Mains/voltage failure stored energy time20 ms
Input current
Rated value at 24 V DC3 A
Rated value at 48 V DC1.5 A
Rated value at 60 V DC1.2 A
Power
Infeed power to the backplane bus60 W; > +60 °C max. power input 30 W
Power loss
Power loss at nominal rating conditions12 W
Interrupts/diagnostics/status information
Status indicatorYes
Potential separation
primary/secondaryYes; Electrical isolation for 230 V AC (reinforced isolation)
Isolation
Isolation tested with2 500 V DC/2 s (routine test)
EMC
Interference immunity against voltage surge
Interference immunity on supply lines acc. to IEC 61000-4-5Yes; ±1 kV (acc. to IEC 61000-4-5; 1995; surge symm.), ±2 kV (acc. to IEC 61000-4-5; 1995; surge asymm.), no external protective circuit required
Degree and class of protection
IP degree of protectionIP20
Equipment protection classI, with protective conductor
Ambient conditions
Ambient temperature during operation
min.-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
max.70 °C; = Tmax; > +60 °C max. power input 30 W; for vertical mounting position Tmax = +40 °C
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width70 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.600 g
Approvals / Certificates