6ES7238-5XA32-0XB0

6ES7238-5XA32-0XB0

SIMATIC S7-1200, аналоговий вхід, SM 1238 Energy Meter 480 В AC, модуль вимірювання потужності для збору даних в одно- та трифазних системах живлення (TN, TT) до 480 В AC; діапазон струму: 1 А, 5 А; вимірювання напруги, струму, фазових кутів, потужності, значень енергії, частот; діагностика каналів.

Категорія товару
Signal modules
Виробник
SIEMENS
Серія продуктів
S7-1200
General information
Product type designationSM 1238, AI energy meter 480 V AC
HW functional statusFrom FS02
Firmware versionV2.0.1
Product function
Voltage measurementYes
with voltage transformerYes
Current measurementYes
without current transformerNo
with current transformerYes
Energy measurementYes
Frequency measurementYes
Power measurementYes
Active power measurementYes
Reactive power measurementYes
I&M dataYes; I&M 0
Isochronous modeNo
Engineering with
STEP 7 TIA Portal configurable/integrated from versionV13 SP1
Operating mode
cyclic measurementYes
acyclic measurementYes
Acyclic measured value accessYes
Fixed measured value setsYes
Freely definable measured value setsNo
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Installation type/mounting
Mounting positionHorizontal, vertical
Supply voltage
Design of the power supplyfrom CPU
Type of supply voltageDC
Input current
Current consumption, max.180 mA
Power loss
Power loss, typ.0.75 W
Address area
Address space per module
Address space per module, max.124 byte; 112 byte input / 12 byte output
Time of day
Operating hours counter
presentYes
Analog inputs
Cycle time (all channels), typ.50 ms; Time for consistent update of all measured and calculated values (cyclic und acyclic data)
Interrupts/diagnostics/status information
Alarms
Diagnostic alarmYes
Limit value alarmYes
Hardware interruptNo
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes
Channel status displayYes; green LED
for channel diagnosticsYes; red Fn LED
for module diagnosticsYes; green/red DIAG LED
Integrated Functions
Measuring functions
Measuring procedure for voltage measurementTRMS
Measuring procedure for current measurementTRMS
Type of measured value acquisitionseamless
Curve shape of voltageSinusoidal or distorted
Buffering of measured variablesYes
Parameter length74 byte
Bandwidth of measured value acquisition2 kHz; Harmonics: 39 / 50 Hz, 32 / 60 Hz
Measuring range
Frequency measurement, min.45 Hz
Frequency measurement, max.65 Hz
Measuring inputs for voltage
Measurable line voltage between phase and neutral conductor277 V
Measurable line voltage between the line conductors480 V
Measurable line voltage between phase and neutral conductor, min.0 V
Measurable line voltage between phase and neutral conductor, max.293 V
Measurable line voltage between the line conductors, min.0 V
Measurable line voltage between the line conductors, max.508 V
Internal resistance line conductor and neutral conductor3.4 MΩ
Power consumption per phase20 mW
Impulse voltage resistance 1,2/50µs1 kV
Measurement category for voltage measurement in accordance with IEC 61010-2-030CAT II; CAT III in case of guaranteed protection level of 1.5 kV
Measuring inputs for current
measurable relative current (AC), min.1 %; Relative to the secondary rated current 5 A
measurable relative current (AC), max.100 %; Relative to the secondary rated current 5 A
Continuous current with AC, maximum permissible5 A
Apparent power consumption per phase for measuring range 5 A0.6 V·A
Rated value short-time withstand current restricted to 1 s100 A
Input resistance measuring range 0 to 5 A25 mΩ; At the terminal
Surge strength10 A; for 1 minute
Zero point suppressionParameterizable: 2 ... 250 mA, default 50 mA
Accuracy class according to IEC 61557-12
Measured variable voltage0,2
Measured variable current0,2
Measured variable apparent power0.5
Measured variable active power0.5
Measured variable reactive power1
Measured variable power factor0.5
Measured variable active energy0.5
Measured variable reactive energy1
Measured variable neutral current0.5; calculated
Measured variable phase angle±1 °; not covered by IEC 61557-12
Measured variable frequency0.05
Potential separation
Potential separation channels
between the channels and backplane busYes; 3 700V AC (type test) CAT III
Isolation
Isolation tested with2 300V AC for 1 min. (type test)
Standards, approvals, certificates
CE markYes
CSA approvalYes
UL approvalYes
cULusYes
FM approvalYes
RCM (formerly C-TICK)Yes
KC approvalYes
Marine approvalYes
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-20 °C
horizontal installation, max.60 °C
vertical installation, min.-20 °C
vertical installation, max.50 °C
Dimensions
Width45 mm
Height100 mm
Depth75 mm
Weights
Weight, approx.165 g
Other
Data for selecting a current transformer
Burden power current transformer x/1A, min.As a function of cable length and cross section, see device manual
Burden power current transformer x/5A, min.As a function of cable length and cross section, see device manual
Approvals / Certificates