6AG1241-1CH32-4XB0

6AG1241-1CH32-4XB0

SIPLUS S7-1200 CM 1241 на основі 6ES7241-1CH32-0XB0 із захисним лакуванням, -25…+60 °C, комунікаційний модуль CM 1241, RS-422/485, 9-контактний D-sub (вилка), підтримує Freeport.

Категорія товару
Communication
Виробник
SIEMENS
Серія продуктів
S7-1200
General information
Product type designationCM 1241 RS 422 / 485
based on6ES7241-1CH32-0XB0
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
Current consumption, max.220 mA; From backplane bus 5 V DC
Power loss
Power loss, typ.1.1 W
Interfaces
Interfaces/bus typeRS 422 / 485 (X.27)
Number of interfaces1
Point-to-point connection
Cable length, max.1 000 m
Integrated protocol driver
FreeportYes
ASCIIYes; Available as library function
Modbus RTU masterYes
Modbus RTU deviceYes
USSYes; Available as library function
Protocols
Integrated protocols
Freeport
Telegram length, max.1 kbyte
Bits per character7 or 8
Number of stop bits1 (Standard), 2
ParityNo parity (standard); even, uneven, mark (parity bit always 1); space (parity bit always 0)
3964 (R)
Telegram length, max.1 kbyte
Bits per character7 or 8
Number of stop bits1 (Standard), 2
ParityNo parity (standard); even, uneven, mark (parity bit always 1); space (parity bit always 0)
Modbus RTU master
Address area1 through 49 999 (Standard Modbus addressing)
max. number of devices247; slave numbers 1 through 247, per MODBUS network segment maximum 32 devices, additional repeaters needed to expand the network to maximum configuration
Modbus RTU device
Address area1 through 49 999 (Standard Modbus addressing)
Interrupts/diagnostics/status information
Diagnostics functionYes
Diagnostics indication LED
for status of the outputsYes
Degree and class of protection
IP degree of protectionIP20
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.-20 °C; = Tmin (incl. condensation/frost); start-up @ 0 °C
max.60 °C; = Tmax
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width30 mm
Height100 mm
Depth75 mm
Weights
Weight, approx.155 g
Approvals / Certificates