6ES7322-1FF01-0AA0

Категорія товару
Цифрові модулі
Виробник
SIEMENS
Серія продуктів
S7-300
Supply voltage
Load voltage L1
Rated value (AC)230 V; 120/230 V AC
permissible range, lower limit (AC)93 V
permissible range, upper limit (AC)264 V
permissible frequency range, lower limit47 Hz
permissible frequency range, upper limit63 Hz
Input current
from load voltage L1 (without load), max.2 mA
from backplane bus 5 V DC, max.100 mA
Power loss
Power loss, typ.8.6 W
Digital outputs
Number of digital outputs8
Short-circuit protectionYes; Fuse 8 A, 250 V; per group
required current for fuse shutdown, min.40 A
Response time, max.300 ms
Controlling a digital inputYes
Size of motor starters according to NEMA, max.5 NEMA compliant
Spare fuses8 A / quick response
Zero-crossing switchYes; Max. 60 V
Switching capacity of the outputs
on lamp load, max.50 W
Output voltage
for signal "1", min.L1 (-1.5 V)
for signal "1" (at max. current), min.L1 (-1.5 V)
for signal "1" (at min. current), min.L1 (-8.5 V)
Output current
for signal "1" rated value2 A
for signal "1" permissible range for 0 to 40 °C, min.10 mA
for signal "1" permissible range for 0 to 40 °C, max.2 A
for signal "1" permissible range for 40 to 60 °C, min.10 mA
for signal "1" permissible range for 40 to 60 °C, max.1 A
for signal "1" minimum load current10 mA
for signal "1" permissible surge current, max.20 A; max. 1 AC cycle
for signal "0" residual current, max.2 mA
Output delay with resistive load
"0" to "1", max.1 AC cycle
"1" to "0", max.1 AC cycle
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.10 Hz
with inductive load, max.0.5 Hz
with inductive load (acc. to IEC 60947-5-1, AC15), max.0.5 Hz
on lamp load, max.1 Hz
Total current of the outputs (per group)
horizontal installation
up to 40 °C, max.4 A
up to 60 °C, max.2 A
vertical installation
up to 40 °C, max.2 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
AlarmsNo
Diagnostics functionYes; Fuse blown or load voltage missing
Alarms
Diagnostic alarmNo
Diagnoses
Wire breakNo
Short-circuitNo
Fuse blownYes
Missing load voltageYes
Diagnostics indication LED
Rated load voltage PWR (green)Yes
Fuse OK FSG (green)Yes
Group error SF (red)Yes
Status indicator digital output (green)Yes
Potential separation
Potential separation digital outputs
between the channelsYes
between the channels, in groups of4
between the channels and backplane busYes; Optocoupler
Isolation
Isolation tested with1 500 V AC
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.275 g
Approvals / Certificates