6AG1326-2BF10-2AB0

SIPLUS S7-300 SM 326 10 F-DO based on 6ES7326-2BF10-0AB0 with conformal coating, -25…+60 °C, 70° with forced convection, digital output 24 V DC/2 A PP, fail-safe digital output for SIMATIC S7F systems, with diagnostic alarm, LVV, 1x 40-pole

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Категорія товару
Цифрові модулі
Виробник
SIEMENS
Серія продуктів
S7-300
General information
based on6ES7326-2BF10-0AB0
Supply voltage
Rated value (DC)24 V; 1L+
Reverse polarity protectionYes
Load voltage L+
Rated value (DC)24 V; 2L+, 3L+
Reverse polarity protectionNo
Input current
from supply voltage 1L+, max.100 mA
from load voltage 2L+ (without load), max.100 mA
from load voltage 3L+ (without load), max.100 mA
from backplane bus 5 V DC, max.100 mA
Power loss
Power loss, typ.6 W
Digital outputs
Number of digital outputs10
Short-circuit protectionYes
Switching capacity of the outputs
on lamp load, max.5 W
Output current
for signal "1" rated value2 A
for signal "1" permissible range for 0 to 40 °C, min.7 mA
for signal "1" permissible range for 0 to 40 °C, max.2.4 A
for signal "1" permissible range for 40 to 60 °C, min.7 mA
for signal "1" permissible range for 40 to 60 °C, max.2.4 A
for signal "0" residual current, max.0.5 mA
Switching frequency
with resistive load, max.25 Hz
with inductive load, max.25 Hz
on lamp load, max.10 Hz
Total current of the outputs (per group)
horizontal installation
up to 40 °C, max.10 A
up to 60 °C, max.6 A
vertical installation
up to 40 °C, max.5 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
Alarms
Diagnostic alarmYes
Diagnoses
Diagnostic information readableYes
Diagnostics indication LED
Fail-safe operationYes
Group error SF (red)Yes
Potential separation
Potential separation digital outputs
between the channelsYes
between the channels, in groups of5
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with370V for 1 min
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Highest safety class achievable in safety mode
acc. to EN 954Cat. 4
Performance level according to ISO 13849-1e
SIL acc. to IEC 61508SIL 3
Ambient conditions
Ambient temperature during operation
min.-25 °C
max.60 °C; = T max; *+70 °C when forced convection at a minimum air speed of 0.3 m/s through the modules is ensured. If in the course of maintenance or automatic diagnosis it is determined that the admissible specified parameters have been exceeded, the modules should be subjected to a proof test (function check) by the manufacturer.
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector40-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.330 g
Approvals / Certificates