6AG1321-7BH01-4AS0

Siemens 6AG1321-7BH01-4AS0

SIPLUS S7-300 SM 321 16 DI based on 6ES7321-7BH01-0AB0 with conformal coating, 0…+60 °C, 0-1 threshold at approx. 11.2 V, digital input SM 321, isolated, 16 DI; 24 V DC, 1x 20-pole, hardware interrupt, diagnostics, suitable for isochronous mode

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Категорія товару
Цифрові модулі
Виробник
SIEMENS
Серія продуктів
S7-300
General information
based on6ES7321-7BH01-0AB0
Product function
Isochronous modeYes
Supply voltage
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.90 mA
from backplane bus 5 V DC, max.130 mA
Encoder supply
Number of outputs2
Type of output voltageL+ (-2.5 V)
Short-circuit protectionYes; Electronic
additional (redundant) feedYes
Output current
Rated value120 mA
permissible range, lower limit0 mA
permissible range, upper limit150 mA
Power loss
Power loss, typ.4 W
Digital inputs
Number of digital inputs16
Input characteristic curve in accordance with IEC 61131, type 2Yes
Number of simultaneously controllable inputs
horizontal installation
up to 60 °C, max.16
vertical installation
up to 40 °C, max.16
Input voltage
Type of input voltageDC
Rated value (DC)24 V
for signal "0"-30 ... +11.2 V
for signal "1"13 to 30V
Input current
for signal "1", typ.7 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizableYes; 0.1 / 0.5 / 3 / 15 / 20 ms
Encoder connection
Fixed current limitation for wire-break monitoring, min.10 kΩ
Fixed current limitation for wire-break monitoring, max.18 kΩ
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Encoder
Connectable encoders
2-wire sensorYes
permissible quiescent current (2-wire sensor), max.2 mA
Interrupts/diagnostics/status information
AlarmsYes
Diagnostics functionYes; Parameterizable
Alarms
Diagnostic alarmYes; Parameterizable
Hardware interruptYes; Parameterizable
Diagnoses
Diagnostic information readableYes
Wire breakYes; to I< 1 mA
Diagnostics indication LED
Group error SF (red)Yes
Status indicator digital input (green)Yes
Encoder supply Vs (green)Yes
Potential separation
Potential separation digital inputs
between the channelsNo
between the channels, in groups of16
between the channels and backplane busYes; Optocoupler
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Ambient conditions
Ambient temperature during operation
min.0 °C; = Tmin
max.60 °C; = Tmax
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.200 g
Approvals / Certificates