6ES7532-5HF00-0AB0

6ES7532-5HF00-0AB0

SIMATIC S7-1500, modul analógových výstupov AQ8xU/I HS, 16-bitové rozlíšenie, presnosť 0.3%, 8 kanálov v skupinách po 8, diagnostika; náhradná hodnota, 8 kanálov za 0.125 ms, oversampling; modul podporuje bezpečnostné vypnutie záťažových skupín do SIL2 podľa EN IEC 62061:2021 a kategórie 3 / PL d podľa EN ISO 13849-1:2015. Dodávka vrátane prívodného elementu, tieniacej konzoly a tieniacej svorky: čelný konektor (skrutkové svorky alebo push-in) sa objednáva samostatne.

Kategória produktu
Analógové moduly
Výrobca
SIEMENS
Produktový rad
S7-1500
General information
Product type designationAQ 8xU/I HS
HW functional statusfrom FS01
Firmware versionV2.1.0
FW update possibleYes
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeYes
Prioritized startupNo
Output range scalableNo
Engineering with
STEP 7 TIA Portal configurable/integrated from versionV14 / -
STEP 7 configurable/integrated from versionV5.5 SP3 / -
PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
PROFINET from GSD version/GSD revisionV2.3 / -
Operating mode
OversamplingYes
MSOYes
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.320 mA; with 19.2 V supply
Power
Power consumption from the backplane bus1.15 W
Power loss
Power loss, typ.7 W
Analog outputs
Number of analog outputs8
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.45 mA
Current output, no-load voltage, max.20 V
Cycle time (all channels), min.125 µs; independent of number of activated channels
Analog output with oversamplingYes
Values per cycle, max.16
Resolution, min.125 µs
Output ranges, voltage
0 to 10 VYes
1 V to 5 VYes
-5 V to +5 VNo
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mAYes
4 mA to 20 mAYes
Connection of actuators
for voltage output two-wire connectionYes
for voltage output four-wire connectionYes
for current output two-wire connectionYes
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ
with voltage outputs, capacitive load, max.100 nF
with current outputs, max.500 Ω
with current outputs, inductive load, max.1 mH
Cable length
shielded, max.200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Conversion time (per channel)50 µs; independent of number of activated channels
Settling time
for resistive load30 µs; see additional description in the manual
for capacitive load100 µs; see additional description in the manual
for inductive load100 µs; see additional description in the manual
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0.02 %
Linearity error (relative to output range), (+/-)0.15 %
Temperature error (relative to output range), (+/-)0.002 %/K
Crosstalk between the outputs, max.-100 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.05 %
note regarding accuracyat temperatures below 0 °C, the figures for operating error and temperature error are doubled
Operational error limit in overall temperature range
Voltage, relative to output range, (+/-)0.3 %
Current, relative to output range, (+/-)0.3 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0.2 %
Current, relative to output range, (+/-)0.2 %
Isochronous mode
Execution and activation time (TCO), min.100 µs
Bus cycle time (TDP), min.250 µs
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnoses
Monitoring the supply voltageYes
Wire breakYes; Only for output type "current"
Short-circuitYes; Only for output type "voltage"
Overflow/UnderflowYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
Monitoring of the supply voltage (PWR-LED)Yes; green LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; red LED
Potential separation
Potential separation channels
between the channelsNo
between the channels, in groups of8
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
between S- and MANA (UCM)8 V DC
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Siemens Eco Profile (SEP)Siemens EcoTech
Suitable for safety-related tripping of standard modulesYes; from FS04
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]37.6 kg
global warming potential, (during production) [CO2 eq]11.1 kg
global warming potential, (during operation) [CO2 eq]26.8 kg
global warming potential, (after end of life cycle) [CO2 eq]-0.364 kg
Highest safety class achievable for safety-related tripping of standard modules
Performance level according to ISO 13849-1PL d
Category according to ISO 13849-1Cat. 3
SIL acc. to IEC 62061SIL 2
remark on safety-oriented shutdownhttps://support.industry.siemens.com/cs/de/en/view/39198632
Security
signed firmware updateNo
securely removing dataNo
data integrityNo
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-30 °C; From FS03
horizontal installation, max.60 °C
vertical installation, min.-30 °C; From FS03
vertical installation, max.40 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Absolute humidity
dew point, min.-60 °C; suitable for dry room applications
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.325 g
Other
Note:please order front connectors (screw-in/push-in) separately
Approvals / Certificates