6AG1215-1HG40-2XB0
SIPLUS S7-1200 CPU 1215C DC/DC/relé na báze 6ES7215-1HG40-0XB0 s ochranným lakovaním, -40…+70 °C, nábeh -25 °C, signálová doska: 0, kompaktná CPU, DC/DC/relé, 2 porty PROFINET, vstavané I/O: 14 DI 24 V DC 10 DQ relé 2 A, 2 AI 0-10 V DC 2 AQ 0-20 mA DC, napájanie: DC 20.4-28.8 V DC, pamäť programu/dát 125 KB
Kategória produktu
CPUZbernicový systém
PROFINETMenovité napätie
24V DCVýrobca
SIEMENSProduktový rad
S7-1200Pracovná pamäť
100 kbyteZavádzacia pamäť
4 MbyteDigitálne vstupy
14 - (24V DC)Digitálne výstupy
10 - (0,5A)Analógové vstupy
2 - (0-10V)Analógové výstupy
2 - (0-20mA)Protokoly
PROFINET IO ControllerPROFINET IO DeviceKrytie (IP)
IP20Stratový výkon
12 WOdber prúdu
500 mA; len CPU| General information | |
|---|---|
| Product type designation | CPU 1215C DC/DC/relay |
| based on | 6ES7215-1HG40-0XB0 |
| Engineering with | |
| STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 |
| Supply voltage | |
| Rated value (DC) | |
| 24 V DC | Yes |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Load voltage L+ | |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Input current | |
| Current consumption (rated value) | 500 mA; CPU only |
| Current consumption, max. | 1 500 mA; CPU with all expansion modules |
| Inrush current, max. | 12 A; at 28.8 V DC |
| I²t | 0.8 A²·s |
| Output current | |
| for backplane bus (5 V DC), max. | 1 600 mA; Max. 5 V DC for SM and CM |
| Encoder supply | |
| 24 V encoder supply | |
| 24 V | L+ minus 4 V DC min. |
| Power loss | |
| Power loss, typ. | 12 W |
| Storage | |
| Work memory | |
| integrated | 200 kbyte |
| Load memory | |
| Integrated | 4 Mbyte |
| Plug-in (SIMATIC Memory Card), max. | with SIMATIC memory card |
| Backup | |
| present | Yes |
| maintenance-free | Yes |
| without battery | Yes |
| CPU processing times | |
| for bit operations, typ. | 0.08 µs; / instruction |
| for word operations, typ. | 1.7 µs; / instruction |
| for floating point arithmetic, typ. | 2.3 µs; / instruction |
| CPU-blocks | |
| Number of elements (total) | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used |
| OB | |
| Number, max. | Limited only by RAM for code |
| Data areas and their retentivity | |
| Retentive data area (incl. timers, counters, flags), max. | 10 kbyte |
| Flag | |
| Size, max. | 8 kbyte; Size of bit memory address area |
| Local data | |
| per priority class, max. | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB |
| Address area | |
| Process image | |
| Inputs, adjustable | 1 kbyte |
| Outputs, adjustable | 1 kbyte |
| Hardware configuration | |
| Number of modules per system, max. | 3 communication modules, no signal board can be used, 8 signal modules |
| number of expansion boards (SB, CB, BB) | 0 |
| number of signal modules (SM) | 8 |
| number of communications modules (CM) | 3 |
| Time of day | |
| Clock | |
| Hardware clock (real-time) | Yes |
| Backup time | 480 h; Typical |
| Deviation per day, max. | ±60 s/month at 25 °C |
| Digital inputs | |
| Number of digital inputs | 14; Integrated |
| of which inputs usable for technological functions | 6; HSC (High Speed Counting) |
| Sourcing/sinking input | Yes |
| Number of simultaneously controllable inputs | |
| all mounting positions | |
| up to 40 °C, max. | 14 |
| Input voltage | |
| Rated value (DC) | 24 V |
| for signal "0" | 5 V DC at 1 mA |
| for signal "1" | 15 V DC at 2.5 mA |
| Input current | |
| for signal "1", typ. | 1 mA |
| Input delay (for rated value of input voltage) | |
| for standard inputs | |
| parameterizable | Yes; 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms |
| at "0" to "1", min. | 0.2 ms |
| at "0" to "1", max. | 12.8 ms |
| for interrupt inputs | |
| Parameterizable | Yes |
| for technological functions | |
| Parameterizable | Yes; Single phase : 3 at 100 kHz & 3 at 30 kHz, differential: 3 at 80 kHz & 3 at 30 kHz |
| Cable length | |
| shielded, max. | 500 m; 50 m for technological functions |
| unshielded, max. | 300 m; for technological functions: No |
| Digital outputs | |
| Number of digital outputs | 10; Relays |
| Switching capacity of the outputs | |
| with resistive load, max. | 2 A |
| on lamp load, max. | 30 W with DC, 200 W with AC |
| Output delay with resistive load | |
| "0" to "1", max. | 10 ms; max. |
| "1" to "0", max. | 10 ms; max. |
| Relay outputs | |
| Number of relay outputs | 10 |
| Number of operating cycles, max. | mechanically 10 million, at rated load voltage 100 000 |
| Cable length | |
| shielded, max. | 500 m |
| unshielded, max. | 150 m |
| Analog inputs | |
| Number of analog inputs | 2 |
| Input ranges | |
| Voltage | Yes |
| Input ranges (rated values), voltages | |
| 0 to +10 V | Yes |
| Input resistance (0 to 10 V) | ≥100k ohms |
| Cable length | |
| shielded, max. | 100 m; twisted and shielded |
| Analog outputs | |
| Number of analog outputs | 2 |
| Output ranges, current | |
| 0 to 20 mA | Yes |
| Analog value generation for the inputs | |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 10 bit |
| Integration time, parameterizable | Yes |
| Conversion time (per channel) | 625 µs |
| Analog value generation for the outputs | |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 10 bit |
| Encoder | |
| Connectable encoders | |
| 2-wire sensor | Yes |
| Interfaces | |
| Number of PROFINET interfaces | 1 |
| 1. Interface | |
| Interface type | PROFINET |
| Isolated | Yes |
| automatic detection of transmission rate | Yes |
| Autonegotiation | Yes |
| Autocrossing | Yes |
| Interface types | |
| RJ 45 (Ethernet) | Yes |
| Number of ports | 2 |
| integrated switch | Yes |
| Protocols | |
| PROFINET IO Controller | Yes |
| PROFINET IO Device | Yes |
| SIMATIC communication | Yes |
| Open IE communication | Yes; Optionally also encrypted |
| Web server | Yes |
| Media redundancy | Yes |
| PROFINET IO Controller | |
| Transmission rate, max. | 100 Mbit/s |
| Services | |
| PG/OP communication | Yes; encryption with TLS V1.3 pre-selected |
| Isochronous mode | No |
| IRT | No |
| PROFIenergy | No |
| Prioritized startup | Yes |
| Number of IO devices with prioritized startup, max. | 16 |
| Number of connectable IO Devices, max. | 16 |
| Number of connectable IO Devices for RT, max. | 16 |
| of which in line, max. | 16 |
| Number of IO Devices that can be simultaneously activated/deactivated, max. | 8 |
| Updating time | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. |
| PROFINET IO Device | |
| Services | |
| PG/OP communication | Yes; encryption with TLS V1.3 pre-selected |
| Isochronous mode | No |
| IRT | No |
| Dynamic Frame Packing (DFP) | No |
| PROFIenergy | Yes |
| Prioritized startup | Yes |
| Shared device | Yes |
| Number of IO Controllers with shared device, max. | 2 |
| Asset management record | Yes |
| Protocols | |
| Supports protocol for PROFINET IO | Yes |
| PROFIsafe | No |
| PROFIBUS | Yes; CM 1243-5 (master) or CM 1242-5 (slave) required |
| OPC UA | Yes; OPC UA Server |
| AS-Interface | Yes; CM 1243-2 required |
| Protocols (Ethernet) | |
| TCP/IP | Yes |
| DHCP | No |
| SNMP | Yes |
| DCP | Yes |
| LLDP | Yes |
| Redundancy mode | |
| PROFINET system redundancy (S2) | No |
| PROFINET system redundancy (R1) | No |
| Media redundancy | |
| MRP | Yes; as MRP redundancy manager and/or MRP client |
| MRP interconnection, supported | No |
| MRPD | No |
| SIMATIC communication | |
| S7 routing | Yes |
| Open IE communication | |
| TCP/IP | Yes |
| Data length, max. | 8 kbyte |
| ISO-on-TCP (RFC1006) | Yes |
| Data length, max. | 8 kbyte |
| UDP | Yes |
| Data length, max. | 1 472 byte |
| Web server | |
| supported | Yes |
| User-defined websites | Yes |
| OPC UA | |
| Runtime license required | Yes; "Basic" license required |
| OPC UA Server | Yes; data access (read, write, subscribe), method call, runtime license required |
| Application authentication | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 |
| User authentication | "anonymous" or by user name & password |
| Number of sessions, max. | 10 |
| Number of subscriptions per session, max. | 5 |
| Sampling interval, min. | 100 ms |
| Publishing interval, min. | 200 ms |
| Number of server methods, max. | 20 |
| Number of monitored items, recommended max. | 1 000 |
| Number of server interfaces, max. | 2 |
| Number of nodes for user-defined server interfaces, max. | 2 000 |
| Further protocols | |
| MODBUS | Yes |
| Communication functions | |
| S7 communication | |
| supported | Yes |
| as server | Yes |
| as client | Yes |
| User data per job, max. | See online help (S7 communication, user data size) |
| Number of connections | |
| overall | PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 68 max |
| Test commissioning functions | |
| Status/control | |
| Status/control variable | Yes |
| Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
| Forcing | |
| Forcing | Yes |
| Diagnostic buffer | |
| present | Yes |
| Traces | |
| Number of configurable Traces | 2 |
| Memory size per trace, max. | 512 kbyte |
| Interrupts/diagnostics/status information | |
| Diagnostics indication LED | |
| RUN/STOP LED | Yes |
| ERROR LED | Yes |
| MAINT LED | Yes |
| Integrated Functions | |
| Counter | |
| Number of counters | 6 |
| Counting frequency, max. | 100 kHz |
| Frequency measurement | Yes |
| controlled positioning | Yes |
| Number of position-controlled positioning axes, max. | 8 |
| PID controller | Yes |
| Number of alarm inputs | 4 |
| Potential separation | |
| Potential separation digital inputs | |
| Potential separation digital inputs | 500 V AC for 1 minute |
| between the channels, in groups of | 1 |
| Potential separation digital outputs | |
| Potential separation digital outputs | Relays |
| between the channels | No |
| between the channels, in groups of | 2 |
| EMC | |
| Interference immunity against discharge of static electricity | |
| Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 | Yes |
| Test voltage at air discharge | 8 kV |
| Test voltage at contact discharge | 6 kV |
| Interference immunity to cable-borne interference | |
| Interference immunity on supply lines acc. to IEC 61000-4-4 | Yes |
| Interference immunity on signal cables acc. to IEC 61000-4-4 | Yes |
| Interference immunity against voltage surge | |
| Interference immunity on supply lines acc. to IEC 61000-4-5 | Yes |
| Interference immunity against conducted variable disturbance induced by high-frequency fields | |
| Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 | Yes |
| Emission of radio interference acc. to EN 55 011 | |
| Limit class A, for use in industrial areas | Yes; Group 1 |
| Limit class B, for use in residential areas | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 |
| Degree and class of protection | |
| IP degree of protection | IP20 |
| Standards, approvals, certificates | |
| Siemens Eco Profile (SEP) | Siemens EcoTech |
| Ecological footprint | |
| environmental product declaration | Yes; type II acc. to ISO 14021 |
| Global warming potential | |
| global warming potential, (total) [CO2 eq] | 106 kg |
| global warming potential, (during production) [CO2 eq] | 18.5 kg |
| global warming potential, (during operation) [CO2 eq] | 88.2 kg |
| global warming potential, (after end of life cycle) [CO2 eq] | -1.1 kg |
| Ambient conditions | |
| Free fall | |
| Fall height, max. | 0.3 m; five times, in product package |
| Ambient temperature during operation | |
| min. | -40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C |
| max. | 70 °C; = Tmax; Tmax > +55 °C number of simultaneously switched-on digital inputs 7, digital outputs 5, analog inputs 2, analog outputs 2 (no adjacent points) with horizontal mounting position; Tmax > +60 °C number of simultaneously switched-on digital inputs 7, digital outputs 5, analog inputs 1, analog outputs 1 (no adjacent points) with horizontal mounting position |
| At cold restart, min. | -25 °C |
| Ambient temperature during storage/transportation | |
| min. | -40 °C |
| max. | 70 °C |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 2 000 m |
| Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m); above 2 000 m max. 132 V AC |
| Relative humidity | |
| With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Vibrations | |
| Vibration resistance during operation acc. to IEC 60068-2-6 | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail |
| Operation, tested according to IEC 60068-2-6 | Yes |
| Shock testing | |
| tested according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms |
| Resistance | |
| Coolants and lubricants | |
| Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air |
| Use in stationary industrial systems | |
| to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
| Use on ships/at sea | |
| to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
| to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
| Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
| Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| Conformal coating | |
| Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability |
| Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
| Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
| Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A |
| Configuration | |
| Programming | |
| Programming language | |
| LAD | Yes |
| FBD | Yes |
| SCL | Yes |
| Know-how protection | |
| User program protection/password protection | Yes |
| Copy protection | Yes |
| Block protection | Yes |
| Access protection | |
| protection of confidential configuration data | Yes |
| Protection level: Write protection | Yes |
| Protection level: Read/write protection | Yes |
| Protection level: Complete protection | Yes |
| User administration | Yes; device-wide |
| Number of users | 42 |
| Number of groups | 14 |
| Number of roles | 20 |
| Cycle time monitoring | |
| can be set | Yes |
| Dimensions | |
| Width | 130 mm |
| Height | 100 mm |
| Depth | 75 mm |
| Weights | |
| Weight, approx. | 585 g |
| Approvals / Certificates | |