6ES7521-1BH00-0AB0

6ES7521-1BH00-0AB0

SIMATIC S7-1500, moduł wejść cyfrowych DI 16x24 V DC HF, 16 kanałów w grupach po 16; z czego 2 wejścia mogą być wykorzystane jako liczniki; opóźnienie wejścia 0.05..20 ms; typ wejścia 3 (IEC 61131); diagnostyka; przerwania sprzętowe: złącze czołowe (zaciski śrubowe lub push-in) należy zamówić odrębnie.

Kategoria produktu
Moduły cyfrowe
Producent
SIEMENS
Seria produktów
S7-1500
General information
Product type designationDI 16x24VDC HF
HW functional statusfrom FS04
Firmware versionV2.2.0
FW update possibleYes
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeYes
Prioritized startupYes
Engineering with
STEP 7 TIA Portal configurable/integrated from versionV13 SP1 / -
STEP 7 configurable/integrated from versionV5.5 SP3 / -
PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
PROFINET from GSD version/GSD revisionV2.3 / -
Operating mode
DIYes
CounterYes
OversamplingNo
MSIYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.20 mA
Power
Power consumption from the backplane bus1.1 W
Power loss
Power loss, typ.2.6 W
Address area
Address space per module
Inputs2 byte; typical, maximum 20 bytes, see manual for details
Outputs0 byte; typical, maximum 16 bytes, see manual for details
Digital inputs
Number of digital inputs16
Digital inputs, parameterizableYes
Sourcing/sinking inputP-reading
Input characteristic curve in accordance with IEC 61131, type 3Yes
Pulse extensionNo
Edge evaluationYes; Positive edge, negative edge
Signal change flutterNo
Flutter observation windowNo
Number of simultaneously controllable inputs
Number of simultaneously controllable inputs16
Digital input functions, parameterizable
Gate start/stopYes
Freely usable digital inputYes
Counter
Number, max.2
Counting frequency, max.6 kHz
Counting width32 bit
Counting direction up/downUp
Digital input with oversamplingNo
Input voltage
Rated value (DC)24 V
for signal "0"-30 to +5 V
for signal "1"+11 to +30V
Input current
for signal "1", typ.2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizableYes; 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms
at "0" to "1", min.0.05 ms
at "0" to "1", max.20 ms
at "1" to "0", min.0.05 ms
at "1" to "0", max.20 ms
for interrupt inputs
ParameterizableYes
for technological functions
ParameterizableYes
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Encoder
Connectable encoders
2-wire sensorYes
permissible quiescent current (2-wire sensor), max.1.5 mA
Isochronous mode
Filtering and processing time (TCI), min.80 µs; At 50 μs filter time
Bus cycle time (TDP), min.250 µs
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Hardware interruptYes
Diagnoses
Monitoring the supply voltageYes
Wire breakYes; to I < 350 µA
Short-circuitNo
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
Monitoring of the supply voltage (PWR-LED)Yes; green LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; red LED
Potential separation
Potential separation channels
between the channelsNo
between the channels, in groups of16
between the channels and backplane busYes
Between the channels and load voltage L+No
between the channels and the power supply of the electronicsNo
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Siemens Eco Profile (SEP)Siemens EcoTech
Suitable for safety functionsNo
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]18.9 kg
global warming potential, (during production) [CO2 eq]12.1 kg
global warming potential, (during operation) [CO2 eq]7.66 kg
global warming potential, (after end of life cycle) [CO2 eq]-1.02 kg
Security
signed firmware updateYes; Firmware V3.0.0 or higher
securely removing dataNo
data integrityYes; Firmware V3.0.0 or higher
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-30 °C; From FS05
horizontal installation, max.60 °C
vertical installation, min.-30 °C; From FS05
vertical installation, max.40 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Absolute humidity
dew point, min.-60 °C; suitable for dry room applications
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.240 g
Other
Note:please order front connectors (screw-in/push-in) separately
Approvals / Certificates