6AG1532-5HD00-7AB0

6AG1532-5HD00-7AB0

SIPLUS S7-1500 AQ 4xU/I ST na bazie 6ES7532-5HD00-0AB0 z powłoką ochronną, -40…+70 °C, moduł wyjść analogowych 16-bit rozdzielczość, dokładność 0.3%. 4 kanałów w grupach po 4, diagnostyka; wartość zastępcza wraz z elementem zasilającym, uchwytem ekranującym i zaciskiem ekranującym.

Kategoria produktu
Moduły analogowe
Producent
SIEMENS
Seria produktów
S7-1500
General information
Product type designationAQ 4xU/I ST
Firmware version
FW update possibleYes
based on6ES7532-5HD00-0AB0
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Prioritized startupNo
Output range scalableNo
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
OversamplingNo
MSOYes
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Input current
Current consumption, max.190 mA; with 24 V DC supply
Power
Power consumption from the backplane bus0.6 W
Power loss
Power loss, typ.4 W
Analog outputs
Number of analog outputs4; > +60 °C max. 4x ±10 V permissible
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.24 mA
Current output, no-load voltage, max.22 V
Cycle time (all channels), min.3.2 ms; independent of number of activated channels
Output ranges, voltage
0 to 10 VYes
1 V to 5 VYes
-5 V to +5 VNo
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mAYes
4 mA to 20 mAYes
Connection of actuators
for voltage output two-wire connectionYes
for voltage output four-wire connectionYes
for current output two-wire connectionYes
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ; 0.5 kOhm at 1 to 5 V
with voltage outputs, capacitive load, max.1 µF
with current outputs, max.750 Ω
with current outputs, inductive load, max.10 mH
Cable length
shielded, max.800 m; for current, 200 m for voltage
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Conversion time (per channel)0.5 ms
Settling time
for resistive load1.5 ms
for capacitive load2.5 ms
for inductive load2.5 ms
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0.02 %
Linearity error (relative to output range), (+/-)0.15 %
Temperature error (relative to output range), (+/-)0.002 %/K
Crosstalk between the outputs, max.-100 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.05 %
Operational error limit in overall temperature range
Voltage, relative to output range, (+/-)0.4 %
Current, relative to output range, (+/-)0.4 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0.2 %
Current, relative to output range, (+/-)0.2 %
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnoses
Monitoring the supply voltageYes
Wire breakYes; Only for output type "current"
Short-circuitYes; Only for output type "voltage"
Overflow/UnderflowYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
Monitoring of the supply voltage (PWR-LED)Yes; green LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; red LED
Potential separation
Potential separation channels
between the channelsNo
between the channels, in groups of4
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
between S- and MANA (UCM)8 V DC
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for safety-related tripping of standard modulesYes; From FS05
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]37.6 kg
global warming potential, (during production) [CO2 eq]11.1 kg
global warming potential, (during operation) [CO2 eq]26.8 kg
global warming potential, (after end of life cycle) [CO2 eq]-0.364 kg
Highest safety class achievable for safety-related tripping of standard modules
Performance level according to ISO 13849-1PL d
Category according to ISO 13849-1Cat. 3
SIL acc. to IEC 62061SIL 2
remark on safety-oriented shutdownhttps://support.industry.siemens.com/cs/de/en/view/39198632
Security
signed firmware updateNo
data integrityNo
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.70 °C; = Tmax
vertical installation, min.-40 °C; = Tmin
vertical installation, max.40 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.310 g
Approvals / Certificates