6AG1350-2AH01-4AE0

SIPLUS S7-300 FM350-2 8 channels based on 6ES7350-2AH01-0AE0 with conformal coating, 0…+60 °C, counter module FM 350-2, 8 channels, 20 kHz, 24 V encoder for counting, frequency measurement, speed measurement, cycle duration measurement, dosing incl. configuration package and electronic documentation on CD-ROM

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Kategoria produktu
Moduły funkcyjne
Producent
SIEMENS
Seria produktów
S7-300
General information
based on6ES7350-2AH01-0AE0
Supply voltage
Auxiliary voltage 1L+, load voltage 2L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
from load voltage L+ (without load), max.150 mA
from backplane bus 5 V DC, max.100 mA
Encoder supply
NAMUR encoder supply
8.2 VYes
Short-circuit protectionYes
Output current, max.200 mA
Power loss
Power loss, typ.10 W
Digital inputs
Number of digital inputs8
Number of NAMUR inputs8
Functions1 each for gate start/ gate stop
Input voltage
for signal "0"-3 to +5V
for signal "1"11 to 30.2 V
Input current
for signal "0", max. (permissible quiescent current)2 mA
for signal "1", typ.9 mA
for NAMUR encoders
for signal "0", max.1.2 mA
for signal "1", min.2.1 mA
Input delay (for rated value of input voltage)
Input frequency, max.20 kHz
for standard inputs
at "0" to "1", max.50 µs
for NAMUR inputs
at "0" to "1", max.50 µs
Cable length
shielded, max.100 m
Digital outputs
Number of digital outputs8
Short-circuit protectionYes
Limitation of inductive shutdown voltage toL+ (-40 V)
Output voltage
for signal "1", min.L+ (-0.8 V)
Output current
for signal "1" rated value0.5 A
for signal "0" residual current, max.0.5 mA
Output delay with resistive load
"0" to "1", max.300 µs
Switching frequency
with resistive load, max.500 Hz
with inductive load, max.0.5 Hz
Total current of the outputs (per group)
horizontal installation
up to 40 °C, max.4 A
up to 60 °C, max.2 A
all other mounting positions
up to 40 °C, max.2 A
Cable length
shielded, max.600 m
unshielded, max.100 m
Encoder
Connectable encoders
Incremental encoder (asymmetrical)Yes
24 V initiatorYes
24 V directional elementYes
NAMUR encoderYes; to DIN 19 234
2-wire sensorYes
Interrupts/diagnostics/status information
Diagnostics functionYes; Diagnostic information readable
Alarms
Diagnostic alarmYes; Parameterizable
Hardware interruptYes; Parameterizable
Diagnostics indication LED
Group error SF (red)Yes
Counter
Number of counter inputs8; 32 bit or ±31 bit
Counter input 24 V
Input voltage for signal "0"-3 to +5V
Input voltage for signal "1"11 to 30.2 V
Input current for signal "1", typ.9 mA
Counting frequency, max.20 kHz; Incremental encoder: 10 kHz
Potential separation
Potential separation digital inputs
between the channels and backplane busYes; and shielding
Potential separation digital outputs
between the channels and backplane busYes; and shielding
Potential separation counter
between the channels and backplane busYes; and shielding
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Ambient conditions
Ambient temperature during operation
min.0 °C; = Tmin
max.60 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector1x 40-pin
Dimensions
Width80 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.460 g