6ES7323-1BH01-0AA0

Kategoria produktu
Moduły cyfrowe
Producent
SIEMENS
Seria produktów
S7-300
Supply voltage
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
from load voltage L+ (without load), max.40 mA
from backplane bus 5 V DC, max.40 mA
Power loss
Power loss, typ.3.5 W
Digital inputs
Number of digital inputs8
Input characteristic curve in accordance with IEC 61131, type 1Yes
Number of simultaneously controllable inputs
horizontal installation
up to 60 °C, max.8
vertical installation
up to 40 °C, max.8
Input voltage
Type of input voltageDC
Rated value (DC)24 V
for signal "0"-30 to +5 V
for signal "1"13 to 30V
Input current
for signal "1", typ.7 mA
Input delay (for rated value of input voltage)
for standard inputs
at "0" to "1", min.1.2 ms
at "0" to "1", max.4.8 ms
at "1" to "0", min.1.2 ms
at "1" to "0", max.4.8 ms
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Digital outputs
Number of digital outputs8
Short-circuit protectionYes
Response threshold, typ.1 A
Limitation of inductive shutdown voltage toL+ (-53 V)
Controlling a digital inputYes
Switching capacity of the outputs
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit4 kΩ
Output voltage
for signal "1", min.L+ (-0.8 V)
Output current
for signal "1" rated value0.5 A
for signal "1" permissible range, min.5 mA
for signal "1" permissible range, max.0.6 A
for signal "1" minimum load current5 mA
for signal "0" residual current, max.0.5 mA
Output delay with resistive load
"0" to "1", max.100 µs
"1" to "0", max.500 µs
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes; only outputs of the same group
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.0.5 Hz
with inductive load (acc. to IEC 60947-5-1, DC13), max.0.5 Hz
on lamp load, max.10 Hz
Total current of the outputs (per group)
horizontal installation
up to 40 °C, max.4 A
up to 60 °C, max.4 A
vertical installation
up to 40 °C, max.4 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Encoder
Connectable encoders
2-wire sensorYes
permissible quiescent current (2-wire sensor), max.2 mA
Interrupts/diagnostics/status information
AlarmsNo
Diagnostics functionNo
Diagnostics indication LED
Status indicator digital input (green)Yes
Status indicator digital output (green)Yes
Potential separation
Potential separation digital inputs
between the channelsYes
between the channels, in groups of8
between the channels and backplane busYes; Optocoupler
Potential separation digital outputs
between the channelsYes
between the channels, in groups of8
between the channels and backplane busYes; Optocoupler
Isolation
Isolation tested with500 V DC
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.220 g
Approvals / Certificates