6AG1322-8BH10-7AB0

Siemens 6AG1322-8BH10-7AB0

SIPLUS S7-300 SM 322 16 DO 24 V DC based on 6ES7322-8BH10-0AB0 with conformal coating, -25…+70 °C, digital output SM 322, 16 DO; 24 V DC/0.5 A, diagnostics-capable, open-circuit detection with 0 and 1 signal, 1x 40-pole, connection IM 153-X HF required

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Kategoria produktu
Moduły cyfrowe
Producent
SIEMENS
Seria produktów
S7-300
General information
based on6ES7322-8BH10-0AB0
Supply voltage
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
from load voltage L+ (without load), max.88 mA
from backplane bus 5 V DC, max.80 mA
Power loss
Power loss, typ.5.7 W
Digital outputs
Number of digital outputs16
Short-circuit protectionYes
Response threshold, typ.1.4 A; per channel
Limitation of inductive shutdown voltage toL+ (-68 V)
Switching capacity of the outputs
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit4 kΩ
Output voltage
for signal "1", min.L+ (-0.7 V)
Output current
for signal "1" rated value0.5 A
for signal "1" permissible range, min.5 mA
for signal "1" permissible range, max.0.6 A
for signal "0" residual current, max.0.7 mA
Output delay with resistive load
"0" to "1", max.3 ms
"1" to "0", max.3 ms
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.100 Hz
with inductive load (acc. to IEC 60947-5-1, DC13), max.2 Hz
on lamp load, max.10 Hz
Total current of the outputs (per group)
horizontal installation
up to 60 °C, max.2 A
up to 70 °C, max.0.5 A
vertical installation
up to 40 °C, max.2 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
AlarmsYes
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Diagnoses
Diagnostic information readableYes
Wire breakYes
Short-circuitYes
Missing load voltageYes
Diagnostics indication LED
Rated load voltage PWR (green)No
Group error SF (red)Yes
Status indicator digital output (green)Yes
Channel fault indicator F (red)Yes
Potential separation
Potential separation digital outputs
between the channelsNo
between the channels, in groups of4
between the channels and backplane busYes
between the channels and the power supply of the electronicsNo
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.70 °C; = Tmax; @ 60°C for UL/ATEX/FM use
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector1x 40-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.350 g
Approvals / Certificates