6AG1341-1AH02-7AE0

SIPLUS S7-300 CP 341 based on 6ES7341-1AH02-0AE0 with conformal coating, -25…+70 °C, communications processor with RS-232C interface (RS-232-C) incl. configuration package on CD-ROM

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Kategoria produktu
Komunikacja
Producent
SIEMENS
Seria produktów
S7-300
General information
based on6ES7341-1AH02-0AE0
Supply voltage
Rated value (DC)
24 V DCYes
Input current
from supply voltage L+, max.100 mA
from backplane bus 5 V DC, max.70 mA
Power loss
Power loss, typ.1.6 W
Power loss, max.2.4 W
Interfaces
Interfaces/bus typeRS 232C (V.24)
Number of interfaces1; Isolated
Transmission rate, min.0.3 kbit/s
Transmission rate, max.115.2 kbit/s
Point-to-point connection
Cable length, max.15 m
supported printersSerial printers
Connector type9-pin sub D connector
Integrated protocol driver
3964 (R)Yes
ASCIIYes
RK 512Yes
Telegram length, max.
3964 (R)4 096 byte
ASCII4 096 byte
RK 5124 096 byte
Transmission speed, RS 232
with 3964 (R) protocol, max.115.2 kbit/s
with ASCII protocol, max.115.2 kbit/s
with printer driver, max.115.2 kbit/s
with RK 512 protocol, max.115.2 kbit/s
Interrupts/diagnostics/status information
Diagnostics indication LED
Receive RxDYes
Transmit TxDYes
Group error SF (red)Yes
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Software
Block
FB length in RAM, max.6 100 byte; Data communication, sending and receiving
Connection method
Design of electrical connection for supply voltage3 screw-type terminals: L+, M, GND
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.300 g
Approvals / Certificates