6ES7334-0CE01-0AA0

Kategoria produktu
Moduły analogowe
Producent
SIEMENS
Seria produktów
S7-300
Supply voltage
Load voltage L+
Rated value (DC)24 V
Input current
from supply and load voltage L+ (without load), max.110 mA
from backplane bus 5 V DC, max.55 mA
Power loss
Power loss, typ.3 W
Analog inputs
Number of analog inputs4
For voltage measurement4
permissible input voltage for voltage input (destruction limit), max.20 V
permissible input current for current input (destruction limit), max.40 mA
Cycle time (all channels) max.5 ms
Input ranges
VoltageYes
CurrentYes
ThermocoupleNo
Resistance thermometerNo
ResistanceNo
Input ranges (rated values), voltages
0 to +10 VYes
Input resistance (0 to 10 V)100 kΩ
Input ranges (rated values), currents
0 to 20 mAYes
Input resistance (0 to 20 mA)50 Ω
Cable length
shielded, max.200 m
Analog outputs
Number of analog outputs2
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.11 mA
Current output, no-load voltage, max.15 V
Output ranges, voltage
0 to 10 VYes
Output ranges, current
0 to 20 mAYes
Load impedance (in rated range of output)
with voltage outputs, min.5 kΩ
with voltage outputs, capacitive load, max.1 µF
with current outputs, max.300 Ω
with current outputs, inductive load, max.1 mH
Cable length
shielded, max.200 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.8 bit
Integration time, parameterizableNo
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.8 bit
Conversion time (per channel)500 µs
Settling time
for resistive load0.3 ms
for capacitive load3 ms
for inductive load0.3 ms
Encoder
Connection of signal encoders
for voltage measurementYes
for current measurement as 2-wire transducerNo
for current measurement as 4-wire transducerYes
Errors/accuracies
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.9 %
Current, relative to input range, (+/-)0.8 %
Voltage, relative to output range, (+/-)0.6 %
Current, relative to output range, (+/-)1 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.7 %
Current, relative to input range, (+/-)0.6 %
Voltage, relative to output range, (+/-)0.5 %
Current, relative to output range, (+/-)0.5 %
Interrupts/diagnostics/status information
AlarmsNo
Diagnostics functionNo
Potential separation
Potential separation analog inputs
between the channels and backplane busNo
Potential separation analog outputs
between the channelsNo
between the channels and backplane busNo
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with500 V DC
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth117 mm
Weights
Weight, approx.285 g
Approvals / Certificates