6ES7332-8TF01-0AB0
SIMATIC DP, HART analog output, SM 332, 8 AO, 0/4 - 20 mA HART for ET200M with IM153-2, IM 153-2, 20-pole functions: firmware update, HART auxiliary variables, redundancy, local diagnostic buffer with time stamping,
Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.
Kategoria produktu
Moduły analogoweProducent
SIEMENSSeria produktów
S7-300| General information | |
|---|---|
| Product function | |
| Isochronous mode | No |
| Supply voltage | |
| Load voltage L+ | |
| Rated value (DC) | 24 V |
| Reverse polarity protection | Yes |
| Input current | |
| from load voltage L+ (without load), max. | 350 mA |
| from backplane bus 5 V DC, max. | 110 mA |
| Power loss | |
| Power loss, typ. | 6 W |
| Analog outputs | |
| Number of analog outputs | 8 |
| Current output, no-load voltage, max. | 24 V |
| Output ranges, current | |
| 0 to 20 mA | Yes |
| -20 mA to +20 mA | No |
| 4 mA to 20 mA | Yes |
| Connection of actuators | |
| for current output two-wire connection | Yes |
| Load impedance (in rated range of output) | |
| with current outputs, max. | 750 Ω |
| with current outputs, inductive load, max. | 10 mH |
| Destruction limits against externally applied voltages and currents | |
| Voltages at the outputs towards MANA | +60/-0.5 V |
| Cable length | |
| shielded, max. | 800 m |
| Analog value generation for the outputs | |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 16 bit |
| Basic execution time of the module (all channels released) | 10 ms; 10 ms in AO mode 50 ms in HART-AO mode |
| Settling time | |
| for resistive load | 0.1 ms |
| for inductive load | 0.5 ms |
| Errors/accuracies | |
| Operational error limit in overall temperature range | |
| Current, relative to output range, (+/-) | 0.2 % |
| Basic error limit (operational limit at 25 °C) | |
| Current, relative to output range, (+/-) | 0.1 % |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Alarms | |
| Diagnostic alarm | Yes |
| Diagnostics indication LED | |
| Group error SF (red) | Yes |
| Potential separation | |
| Potential separation analog outputs | |
| between the channels | No |
| between the channels and backplane bus | Yes |
| Between the channels and load voltage L+ | Yes |
| Isolation | |
| Isolation tested with | 500 V DC |
| Degree and class of protection | |
| IP degree of protection | IP20 |
| Connection method | |
| required front connector | 20-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 117 mm |
| Weights | |
| Weight, approx. | 220 g |
| Approvals / Certificates | |