6ES7332-5TB10-0AB0

Siemens 6ES7332-5TB10-0AB0

SIMATIC DP, HART analog output, SM 332, 2 AO, 0/4 - 20 mA HART from HART revision 5.0, for ET200M with IM 153-2, 1 x 20-pole

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Kategoria produktu
Moduły analogowe
Producent
SIEMENS
Seria produktów
S7-300
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.150 mA
from backplane bus 5 V DC, max.100 mA
Power loss
Power loss, typ.3.5 W
Analog outputs
Number of analog outputs2
Current output, no-load voltage, max.19 V
Cycle time (all channels) max.5 ms
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mANo
4 mA to 20 mAYes
Connection of actuators
for current output two-wire connectionYes
Load impedance (in rated range of output)
with current outputs, max.650 Ω
with current outputs, inductive load, max.7.5 mH
Destruction limits against externally applied voltages and currents
Voltages at the outputs towards MANAmax. 17 V / -0.5 V
Current, max.60 mA / -1 A
Cable length
shielded, max.400 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit; + sign
Conversion time (per channel)40 ms
Settling time
for resistive load2.5 ms
for capacitive load4 ms
for inductive load2.5 ms
Errors/accuracies
Operational error limit in overall temperature range
Current, relative to output range, (+/-)0.55 %
Basic error limit (operational limit at 25 °C)
Current, relative to output range, (+/-)0.15 %
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Substitute values connectableYes; Parameterizable
Alarms
Diagnostic alarmYes; Parameterizable
Diagnoses
OverrangeYes
Wire breakYes; as of output value > 0.5 mA
HART communication activeYes; green LED (H)
Diagnostics indication LED
Group error SF (red)Yes; red LED
Channel fault indicator F (red)Yes; per channel
Ex(i) characteristics
Module for Ex(i) protectionYes
maximum values for connecting terminals for gas group IIC
Uo (no-load voltage), max.19 V
Io (short-circuit current), max.66 mA
Po (power output), max.506 mW
Co (permissible external capacity), max.230 nF
Lo (permissible external inductivity), max.7.5 mH
Um (voltage at non-intrinsically safe connecting terminals), max.60 V; DC
Potential separation
Potential separation analog outputs
between the channelsYes
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
between the outputs (UCM)60 V DC/30 V AC permitted potential difference (Viso) of signals from hazardous areas
Degree and class of protection
IP degree of protectionIP20
Standards, approvals, certificates
Use in hazardous areas
ATEX markingATEX II 3 G (2) GD Ex nA [ib Gb] [ib IIIC Db] IIC T4 Gc
ATEX certificateDEKRA 14 ATEX 0053X
FM markingClass I, Division 2, Group A, B, C, D T4; Class I, Zone 2, Group IIC T4
Ambient conditions
Ambient temperature during operation
max.60 °C
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.290 g
Approvals / Certificates