6ES7332-5TB10-0AB0
SIMATIC DP, HART analog output, SM 332, 2 AO, 0/4 - 20 mA HART from HART revision 5.0, for ET200M with IM 153-2, 1 x 20-pole
Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.
Kategoria produktu
Moduły analogoweProducent
SIEMENSSeria produktów
S7-300| Supply voltage | |
|---|---|
| Load voltage L+ | |
| Rated value (DC) | 24 V |
| Reverse polarity protection | Yes |
| Input current | |
| from load voltage L+ (without load), max. | 150 mA |
| from backplane bus 5 V DC, max. | 100 mA |
| Power loss | |
| Power loss, typ. | 3.5 W |
| Analog outputs | |
| Number of analog outputs | 2 |
| Current output, no-load voltage, max. | 19 V |
| Cycle time (all channels) max. | 5 ms |
| Output ranges, current | |
| 0 to 20 mA | Yes |
| -20 mA to +20 mA | No |
| 4 mA to 20 mA | Yes |
| Connection of actuators | |
| for current output two-wire connection | Yes |
| Load impedance (in rated range of output) | |
| with current outputs, max. | 650 Ω |
| with current outputs, inductive load, max. | 7.5 mH |
| Destruction limits against externally applied voltages and currents | |
| Voltages at the outputs towards MANA | max. 17 V / -0.5 V |
| Current, max. | 60 mA / -1 A |
| Cable length | |
| shielded, max. | 400 m |
| Analog value generation for the outputs | |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 12 bit; + sign |
| Conversion time (per channel) | 40 ms |
| Settling time | |
| for resistive load | 2.5 ms |
| for capacitive load | 4 ms |
| for inductive load | 2.5 ms |
| Errors/accuracies | |
| Operational error limit in overall temperature range | |
| Current, relative to output range, (+/-) | 0.55 % |
| Basic error limit (operational limit at 25 °C) | |
| Current, relative to output range, (+/-) | 0.15 % |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes; Parameterizable |
| Substitute values connectable | Yes; Parameterizable |
| Alarms | |
| Diagnostic alarm | Yes; Parameterizable |
| Diagnoses | |
| Overrange | Yes |
| Wire break | Yes; as of output value > 0.5 mA |
| HART communication active | Yes; green LED (H) |
| Diagnostics indication LED | |
| Group error SF (red) | Yes; red LED |
| Channel fault indicator F (red) | Yes; per channel |
| Ex(i) characteristics | |
| Module for Ex(i) protection | Yes |
| maximum values for connecting terminals for gas group IIC | |
| Uo (no-load voltage), max. | 19 V |
| Io (short-circuit current), max. | 66 mA |
| Po (power output), max. | 506 mW |
| Co (permissible external capacity), max. | 230 nF |
| Lo (permissible external inductivity), max. | 7.5 mH |
| Um (voltage at non-intrinsically safe connecting terminals), max. | 60 V; DC |
| Potential separation | |
| Potential separation analog outputs | |
| between the channels | Yes |
| between the channels and backplane bus | Yes |
| Between the channels and load voltage L+ | Yes |
| Permissible potential difference | |
| between the outputs (UCM) | 60 V DC/30 V AC permitted potential difference (Viso) of signals from hazardous areas |
| Degree and class of protection | |
| IP degree of protection | IP20 |
| Standards, approvals, certificates | |
| Use in hazardous areas | |
| ATEX marking | ATEX II 3 G (2) GD Ex nA [ib Gb] [ib IIIC Db] IIC T4 Gc |
| ATEX certificate | DEKRA 14 ATEX 0053X |
| FM marking | Class I, Division 2, Group A, B, C, D T4; Class I, Zone 2, Group IIC T4 |
| Ambient conditions | |
| Ambient temperature during operation | |
| max. | 60 °C |
| Connection method | |
| required front connector | 20-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights | |
| Weight, approx. | 290 g |
| Approvals / Certificates | |