SIPLUS S7-300 SM 332 4 AO U/I based on 6ES7332-5HD01-0AB0 with conformal coating, -25…+70 °C, analog output SM 332, isolated, 4 AO, U/I; diagnostics; resolution 11/12 bits, 20-pole, removing and inserting with active backplane bus possible

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Kategoria produktu
Moduły analogowe
Producent
SIEMENS
Seria produktów
S7-300
General information
based on6ES7332-5HD01-0AB0
Product function
Isochronous modeNo
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.240 mA
from backplane bus 5 V DC, max.60 mA
Power loss
Power loss, typ.3 W
Analog outputs
Number of analog outputs4
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.25 mA
Current output, no-load voltage, max.18 V
Output ranges, voltage
0 to 10 VYes
1 V to 5 VYes
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mAYes
4 mA to 20 mAYes
Connection of actuators
for voltage output four-wire connectionYes
for current output two-wire connectionYes
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ
with voltage outputs, capacitive load, max.1 µF
with current outputs, max.500 Ω
with current outputs, inductive load, max.10 mH
Cable length
shielded, max.200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit; ±10 V, ±20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit
Conversion time (per channel)0.8 ms
Settling time
for resistive load0.2 ms
for capacitive load3.3 ms
for inductive load0.5 ms; 0.5 ms (1 mH); 3.3 ms (10 mH)
Errors/accuracies
Operational error limit in overall temperature range
Voltage, relative to output range, (+/-)0.5 %; ±0.6 % @ < 0 °C or > 60 °C
Current, relative to output range, (+/-)0.6 %; ±0.7 % @ < 0 °C or > 60 °C
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0.4 %
Current, relative to output range, (+/-)0.5 %
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Substitute values connectableYes; Parameterizable
Alarms
Diagnostic alarmYes; Parameterizable
Diagnoses
Diagnostic information readableYes
Diagnostics indication LED
Group error SF (red)Yes
Potential separation
Potential separation analog outputs
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+Yes
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50121-4No
EN 50155No
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.220 g
Approvals / Certificates