6AG1331-7RD00-2AB0

SIPLUS S7-300 SM 331 4AI based on 6ES7331-7RD00-0AB0 with conformal coating, -25…+70 °C, (70° only 4-wire),

Kategoria produktu
Moduły analogowe
Producent
SIEMENS
Seria produktów
S7-300
General information
based on6ES7331-7RD00-0AB0
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.250 mA
from backplane bus 5 V DC, max.60 mA
Output voltage
Power supply to the transmitters
Rated value (DC)13 V; at 22 mA
Power loss
Power loss, typ.3 W
Analog inputs
Number of analog inputs4
permissible input current for current input (destruction limit), max.40 mA
Input ranges
VoltageNo
CurrentYes
ThermocoupleNo
Resistance thermometerNo
ResistanceNo
Input ranges (rated values), currents
0 to 20 mAYes
Input resistance (0 to 20 mA)50 Ω
4 mA to 20 mAYes
Input resistance (4 mA to 20 mA)50 Ω
Cable length
shielded, max.200 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit; 10 bit to 15 bit + sign
Integration time, parameterizableYes; 2.5 to 100 ms
Interference voltage suppression for interference frequency f1 in Hz10 to 400 Hz
Encoder
Connection of signal encoders
for current measurement as 2-wire transducerYes
for current measurement as 4-wire transducerYes
Errors/accuracies
Operational error limit in overall temperature range
Current, relative to input range, (+/-)0.45 %
Basic error limit (operational limit at 25 °C)
Current, relative to input range, (+/-)0.1 %
Interrupts/diagnostics/status information
Diagnostics functionYes
Diagnoses
Diagnostic information readableYes
OverrangeYes
Wire-break in signal transmitter cableYes
Short-circuit of the signal encoder cableYes
Diagnostics indication LED
Group error SF (red)Yes
Channel fault indicator F (red)Yes
Ex(i) characteristics
Module for Ex(i) protectionYes
maximum values for connecting terminals for gas group IIC
Uo (no-load voltage), max.25.2 V
Io (short-circuit current), max.68.5 mA
Po (power output), max.431 mW
Co (permissible external capacity), max.90 nF
Lo (permissible external inductivity), max.7.5 mH
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Use in hazardous areas
ATEX markingATEX II 3 G (2) GD Ex nA [ib Gb] [ib IIIC Db] IIC T4 Gc
FM markingClass I, Division 2, Group A, B, C, D T4
Test number PTBEx-96.D.2092X
Railway application
EN 50121-4No
EN 50155No
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.60 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use, 70 °C only 4 wire
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.290 g
Approvals / Certificates