6AG1331-7PF11-4AB0

SIPLUS S7-300 SM 331 8 AI 40-pole based on 6ES7331-7PF11-0AB0 with conformal coating, 0…+60 °C, analog input isolated, 8 AI thermocouples type B, E, J, K, L, N, R, S, T TXK/TXK (L) according to GOST 16 bit, 50 ms, 1x 40-pole

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Kategoria produktu
Moduły analogowe
Producent
SIEMENS
Seria produktów
S7-300
General information
based on6ES7331-7PF11-0AB0
Product function
Isochronous modeNo
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.240 mA
from backplane bus 5 V DC, max.100 mA
Power loss
Power loss, typ.3 W
Analog inputs
Number of analog inputs8
permissible input voltage for voltage input (destruction limit), max.75 V; 20 V DC permanent, 75 V DC for max. 1 s (duty factor 1:20)
Constant measurement current for resistance-type transmitter, typ.0.7 mA
Input ranges
VoltageNo
CurrentNo
ThermocoupleYes
Resistance thermometerNo
ResistanceNo
Input ranges (rated values), voltages
0 to +10 VNo
1 V to 5 VNo
1 V to 10 VNo
-1 V to +1 VNo
-10 V to +10 VNo
-2.5 V to +2.5 VNo
-250 mV to +250 mVNo
-5 V to +5 VNo
-50 mV to +50 mVNo
-500 mV to +500 mVNo
-80 mV to +80 mVNo
Input ranges (rated values), currents
0 to 20 mANo
-10 mA to +10 mANo
-20 mA to +20 mANo
-3.2 mA to +3.2 mANo
4 mA to 20 mANo
Input ranges (rated values), thermocouples
type BYes
type CYes
Type EYes
Type JYes
Type KYes
Type LYes
Type NYes
Type RYes
Type SYes
Type TYes
Type UYes
Type TXK/TXK(L) to GOSTYes
Input ranges (rated values), resistance thermometer
Cu 10No
Ni 100No
Ni 1000No
LG-Ni 1000No
Ni 120No
Ni 200No
Ni 500No
Pt 100No
Pt 1000No
Pt 200No
Pt 500No
Input ranges (rated values), resistors
0 to 150 ohmsNo
0 to 300 ohmsNo
0 to 600 ohmsNo
0 to 6000 ohmsNo
Thermocouple (TC)
Temperature compensation
ParameterizableYes
internal temperature compensationYes
external temperature compensation with Pt100Yes
external temperature compensation with compensations socketYes
for definable comparison point temperatureYes
Characteristic linearization
ParameterizableYes
for thermocouplesType B, E, J, K, L, N, R, S. T, U, C
Cable length
shielded, max.100 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit; Two's complement
Integration time, parameterizableYes
Basic conversion time (ms)up to 4 channels: 10 ms per module, over 5 channels: 190 ms per module, 8 channels: 80 ms
Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 Hz
Errors/accuracies
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)±1 K
Thermocouple, relative to input range, (+/-)Type T: ±0.18%, Type U: ±0.15%, Type E: ±0.12%, Type J: ±0.12%, Type L: ±0.17%, Type K: ±0.15%, Type N: ±0.17%, Type R: ±0.08%, Type S: ±0.10%, Type B: ±0.13%, Type C: ±0.10%, TXK/XK(L): ±1.00% accuracy in the lower range of the characteristic curve
Basic error limit (operational limit at 25 °C)
Thermocouple, relative to input range, (+/-)Type T: ±0.13%, Type U: ±0.08%, Type E: ±0.05%, Type J: ±0.04%, Type L: ±0.06%, Type K: ±0.04%, Type N: ±0.04%, Type R: ±0.03%, Type S: ±0.03%, Type B: ±0.05%, Type C: ±0.02%, TXK/XK(L): ±0.67 % accuracy in the lower range of the characteristic curve
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Alarms
Diagnostic alarmYes; Parameterizable per group
Limit value alarmYes; Parameterizable
Hardware interruptYes; Parameterizable, channels 0 to 7
Diagnoses
Diagnostic information readableYes
Diagnostics indication LED
Group error SF (red)Yes
Potential separation
Potential separation analog inputs
between the channelsNo
between the channels, in groups of2
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50121-4No
EN 50155No
Ambient conditions
Ambient temperature during operation
min.0 °C; = Tmin
max.60 °C; = Tmax
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector40-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.272 g
Approvals / Certificates