6AG1323-1BH01-2AA0

SIPLUS S7-300 SM 323 20-pole based on 6ES7323-1BH01-0AA0 with conformal coating, -40…+70 °C, digital module isolated 8 DI and 8 DO, 24 V DC, 0.5 A total current 2 A

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Termékkategória
Digitális modulok
Gyártó
SIEMENS
Termékcsalád
S7-300
General information
based on6ES7323-1BH01-0AA0
Supply voltage
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
from load voltage L+ (without load), max.40 mA
from backplane bus 5 V DC, max.40 mA
Power loss
Power loss, typ.3.5 W
Digital inputs
Number of digital inputs8
Input characteristic curve in accordance with IEC 61131, type 1Yes
Number of simultaneously controllable inputs
horizontal installation
up to 60 °C, max.8
vertical installation
up to 40 °C, max.8
Input voltage
Type of input voltageDC
Rated value (DC)24 V
for signal "0"-30 to +5 V
for signal "1"13 to 30V
Input current
for signal "1", typ.7 mA
Input delay (for rated value of input voltage)
for standard inputs
at "0" to "1", min.1.2 ms
at "0" to "1", max.4.8 ms
at "1" to "0", min.1.2 ms
at "1" to "0", max.4.8 ms
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Digital outputs
Number of digital outputs8
Short-circuit protectionYes
Response threshold, typ.1 A
Limitation of inductive shutdown voltage toL+ (-53 V)
Controlling a digital inputYes
Switching capacity of the outputs
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit4 kΩ
Output voltage
for signal "1", min.L+ (-0.8 V)
Output current
for signal "1" rated value0.5 A
for signal "1" permissible range, min.5 mA
for signal "1" permissible range, max.0.6 A
for signal "1" minimum load current5 mA
for signal "0" residual current, max.0.5 mA
Output delay with resistive load
"0" to "1", max.100 µs
"1" to "0", max.500 µs
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes; only outputs of the same group
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.0.5 Hz
with inductive load (acc. to IEC 60947-5-1, DC13), max.0.5 Hz
on lamp load, max.10 Hz
Total current of the outputs (per group)
horizontal installation
up to 60 °C, max.4 A
vertical installation
up to 40 °C, max.4 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Encoder
Connectable encoders
2-wire sensorYes
permissible quiescent current (2-wire sensor), max.2 mA
Interrupts/diagnostics/status information
AlarmsNo
Diagnostics functionNo
Diagnostics indication LED
Status indicator digital input (green)Yes
Status indicator digital output (green)Yes
Potential separation
Potential separation digital inputs
between the channelsYes
between the channels, in groups of8
between the channels and backplane busYes; Optocoupler
Potential separation digital outputs
between the channelsYes
between the channels, in groups of8
between the channels and backplane busYes; Optocoupler
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50155Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B, EN 50155:2007 (see SIOS entry 109755985)
Ambient conditions
Ambient temperature during operation
min.-40 °C; = Tmin
max.70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on land craft, rail vehicles and special-purpose vehicles
to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 50155 (ST2); *
to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.220 g
Approvals / Certificates