6ES7332-5HD01-0AB0

Siemens 6ES7332-5HD01-0AB0

SIMATIC S7-300, analog output SM 332, isolated, 4 AO, U/I; diagnostics; resolution 11/12 bits, 20-pole, removing and inserting with active backplane bus possible

Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.

Termékkategória
Analóg modulok
Gyártó
SIEMENS
Termékcsalád
S7-300
General information
Product function
Isochronous modeNo
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.240 mA
from backplane bus 5 V DC, max.60 mA
Power loss
Power loss, typ.3 W
Analog outputs
Number of analog outputs4
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.25 mA
Current output, no-load voltage, max.18 V
Output ranges, voltage
0 to 10 VYes
1 V to 5 VYes
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mAYes
4 mA to 20 mAYes
Connection of actuators
for voltage output four-wire connectionYes
for current output two-wire connectionYes
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ
with voltage outputs, capacitive load, max.1 µF
with current outputs, max.500 Ω
with current outputs, inductive load, max.10 mH
Cable length
shielded, max.200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit; ±10 V, ±20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit
Conversion time (per channel)0.8 ms
Settling time
for resistive load0.2 ms
for capacitive load3.3 ms
for inductive load0.5 ms; 0.5 ms (1 mH); 3.3 ms (10 mH)
Errors/accuracies
Operational error limit in overall temperature range
Voltage, relative to output range, (+/-)0.5 %
Current, relative to output range, (+/-)0.6 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0.4 %
Current, relative to output range, (+/-)0.5 %
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Substitute values connectableYes; Parameterizable
Alarms
Diagnostic alarmYes; Parameterizable
Diagnoses
Diagnostic information readableYes
Diagnostics indication LED
Group error SF (red)Yes
Potential separation
Potential separation analog outputs
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+Yes
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with500 V DC
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth117 mm
Weights
Weight, approx.220 g