6ES7540-1AB01-0AA0

6ES7540-1AB01-0AA0

SIMATIC S7-1500, CM PTP RS422/485 BA, Kommunikationsmodul für serielle Verbindung RS-422 und RS-485, Freeport, 3964(R), USS, 19200 bit/s, 15-poliger D-Sub-Steckverbinder

Produktkategorie
Communication
Hersteller
SIEMENS
Produktreihe
S7-1500
General information
Product type designationCM PtP RS 422 / 485 BA
Product function
I&M dataYes; I&M 0
Fast startupYes
Engineering with
STEP 7 TIA Portal configurable/integrated from versionV18 with HSP 0367 / V19; with older TIA Portal versions configurable as 6ES7540-1AB00-0AA0
STEP 7 configurable/integrated from versionV5.5 SP2 with GSD file
PROFIBUS from GSD version/GSD revision- / -
PROFINET from GSD version/GSD revisionGSDML V2.42
Installation type/mounting
Rail mountingYes; S7-1500 mounting rail
Input current
Current consumption (rated value)43 mA; From the backplane bus
Power
Power consumption from the backplane bus0.65 W
Power loss
Power loss, typ.0.6 W
Address area
Address space per module
Inputs8 byte; performance mode: 32 byte
Outputs0 byte; performance mode: 32 byte
Interface types
RS 485
Transmission rate, max.19.2 kbit/s
Cable length, max.1 200 m
RS 422
Transmission rate, max.19.2 kbit/s
Cable length, max.1 200 m
4-wire full duplex connectionYes
4-wire multipoint connectionNo
Protocols
Integrated protocols
Freeport
Telegram length, max.1 kbyte
Bits per character7 or 8
Number of stop bits1 or 2 bit
ParityNone, even, odd, always 1, always 0, any
3964 (R)
Telegram length, max.1 kbyte
Bits per character7 or 8
Number of stop bits1 or 2 bit
ParityNone, even, odd, always 1, always 0, any
Telegram buffer
Buffer memory for telegrams2 kbyte
Number of telegrams which can be buffered255
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Hardware interruptNo
Diagnoses
Wire breakYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
Receive RxDYes; Yellow LED
Transmit TxDYes; Yellow LED
Potential separation
between backplane bus and interfaceYes
Isolation
Isolation tested with707 V DC (type test)
Security
signed firmware updateYes
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-30 °C
horizontal installation, max.60 °C
vertical installation, min.-30 °C
vertical installation, max.40 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200MP system manual
Absolute humidity
dew point, min.-60 °C; suitable for dry room applications
Decentralized operation
to SIMATIC S7-300Yes
to SIMATIC S7-400Yes
to SIMATIC S7-1500Yes
to standard PROFINET controllerYes
Dimensions
Width35 mm
Height147 mm
Depth127 mm
Weights
Weight, approx.0.22 kg
Approvals / Certificates