6ES7540-1AB01-0AA0
SIMATIC S7-1500, CM PTP RS422/485 BA, Kommunikationsmodul für serielle Verbindung RS-422 und RS-485, Freeport, 3964(R), USS, 19200 bit/s, 15-poliger D-Sub-Steckverbinder
Produktkategorie
CommunicationHersteller
SIEMENSProduktreihe
S7-1500| General information | |
|---|---|
| Product type designation | CM PtP RS 422 / 485 BA |
| Product function | |
| I&M data | Yes; I&M 0 |
| Fast startup | Yes |
| Engineering with | |
| STEP 7 TIA Portal configurable/integrated from version | V18 with HSP 0367 / V19; with older TIA Portal versions configurable as 6ES7540-1AB00-0AA0 |
| STEP 7 configurable/integrated from version | V5.5 SP2 with GSD file |
| PROFIBUS from GSD version/GSD revision | - / - |
| PROFINET from GSD version/GSD revision | GSDML V2.42 |
| Installation type/mounting | |
| Rail mounting | Yes; S7-1500 mounting rail |
| Input current | |
| Current consumption (rated value) | 43 mA; From the backplane bus |
| Power | |
| Power consumption from the backplane bus | 0.65 W |
| Power loss | |
| Power loss, typ. | 0.6 W |
| Address area | |
| Address space per module | |
| Inputs | 8 byte; performance mode: 32 byte |
| Outputs | 0 byte; performance mode: 32 byte |
| Interface types | |
| RS 485 | |
| Transmission rate, max. | 19.2 kbit/s |
| Cable length, max. | 1 200 m |
| RS 422 | |
| Transmission rate, max. | 19.2 kbit/s |
| Cable length, max. | 1 200 m |
| 4-wire full duplex connection | Yes |
| 4-wire multipoint connection | No |
| Protocols | |
| Integrated protocols | |
| Freeport | |
| Telegram length, max. | 1 kbyte |
| Bits per character | 7 or 8 |
| Number of stop bits | 1 or 2 bit |
| Parity | None, even, odd, always 1, always 0, any |
| 3964 (R) | |
| Telegram length, max. | 1 kbyte |
| Bits per character | 7 or 8 |
| Number of stop bits | 1 or 2 bit |
| Parity | None, even, odd, always 1, always 0, any |
| Telegram buffer | |
| Buffer memory for telegrams | 2 kbyte |
| Number of telegrams which can be buffered | 255 |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Alarms | |
| Diagnostic alarm | Yes |
| Hardware interrupt | No |
| Diagnoses | |
| Wire break | Yes |
| Diagnostics indication LED | |
| RUN LED | Yes; green LED |
| ERROR LED | Yes; red LED |
| Receive RxD | Yes; Yellow LED |
| Transmit TxD | Yes; Yellow LED |
| Potential separation | |
| between backplane bus and interface | Yes |
| Isolation | |
| Isolation tested with | 707 V DC (type test) |
| Security | |
| signed firmware update | Yes |
| Ambient conditions | |
| Ambient temperature during operation | |
| horizontal installation, min. | -30 °C |
| horizontal installation, max. | 60 °C |
| vertical installation, min. | -30 °C |
| vertical installation, max. | 40 °C |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200MP system manual |
| Absolute humidity | |
| dew point, min. | -60 °C; suitable for dry room applications |
| Decentralized operation | |
| to SIMATIC S7-300 | Yes |
| to SIMATIC S7-400 | Yes |
| to SIMATIC S7-1500 | Yes |
| to standard PROFINET controller | Yes |
| Dimensions | |
| Width | 35 mm |
| Height | 147 mm |
| Depth | 127 mm |
| Weights | |
| Weight, approx. | 0.22 kg |
| Approvals / Certificates | |