6AG1522-1BF00-7AB0

6AG1522-1BF00-7AB0

SIPLUS S7-1500 DQ 8x24VDC/2A na bázi 6ES7522-1BF00-0AB0 s ochranným lakováním, -40…+70 °C, modul digitálních výstupů, 8 kanálů ve skupinách po 8; 8 A na skupinu; diagnostika; náhradní hodnota.

Kategorie produktu
Digitální moduly
Výrobce
SIEMENS
Produktová řada
S7-1500
General information
Product type designationDQ 8x24VDC/2A HF
Firmware version
FW update possibleYes
based on6ES7522-1BF00-0AB0
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Prioritized startupYes
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
DQYes
DQ with energy-saving functionYes; with an application
PWMYes
Cam control (switching at comparison values)No
OversamplingNo
MSOYes
Integrated operating cycle counterYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes; through internal protection with 10 A per group
Input current
Current consumption, max.40 mA; 20 mA per group, no output is activated.
Output voltage
Rated value (DC)24 V
Power
Power consumption from the backplane bus0.9 W
Power loss
Power loss, typ.5.6 W; 6.8 W for PWM operation
Digital outputs
Type of digital outputTransistor
Number of digital outputs8; > +60 °C Number of simultaneously controllable outputs max. 8x 0.5 A, max. total current per group 2 A
Current-sourcingYes
Digital outputs, parameterizableYes
output type acc. to IEC 61131, type 2Yes
Short-circuit protectionYes
Response threshold, typ.3 A
Limitation of inductive shutdown voltage to-17 V
Controlling a digital inputYes
Digital output functions, parameterizable
Freely usable digital outputYes
PWM outputYes; FS02 and FW V2.1.0 or higher
Number, max.2
Cycle duration, parameterizableYes; 2 ... 100 ms continuous
ON period, min.0 %
ON period, max.100 %
Resolution of the duty cycle0.1 %
Minimum pulse duration300 µs
Switching capacity of the outputs
on lamp load, max.10 W
Load resistance range
lower limit12 Ω
upper limit4 kΩ
Output voltage
for signal "1", min.L+ (-0.8 V)
Output current
for signal "1" rated value2 A
for signal "1" permissible range, max.2.4 A; note derating specification for PWM operation
for signal "0" residual current, max.0.5 mA
Output delay with resistive load
"0" to "1", typ.80 µs
"0" to "1", max.100 µs
"1" to "0", typ.300 µs
"1" to "0", max.500 µs
Parallel switching of two outputs
for logic linksYes
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.100 Hz; With PWM operation: 500 Hz
with inductive load, max.0.5 Hz; According to IEC 60947-5-1, DC-13; max. 500 Hz with PWM operation only with external circuit; see additional description in the manual
on lamp load, max.10 Hz
Total current of the outputs
Current per channel, max.2 A; see additional description in the manual
Current per group, max.8 A; see additional description in the manual
Current per module, max.16 A; see additional description in the manual
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Maintenance interruptYes
Diagnoses
Monitoring the supply voltageYes
Wire breakNo
Short-circuitYes
Group errorYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
MAINT LEDYes; Yellow LED
Monitoring of the supply voltage (PWR-LED)Yes; green LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; red LED
Potential separation
Potential separation channels
between the channelsNo
between the channels, in groups of4
between the channels and backplane busYes
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functionsNo
Suitable for safety-related tripping of standard modulesYes; From FS03
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]43.8 kg
global warming potential, (during production) [CO2 eq]9.5 kg
global warming potential, (during operation) [CO2 eq]34.5 kg
global warming potential, (after end of life cycle) [CO2 eq]-0.231 kg
Highest safety class achievable for safety-related tripping of standard modules
Performance level according to ISO 13849-1PL d
Category according to ISO 13849-1Cat. 3
SIL acc. to IEC 62061SIL 2
remark on safety-oriented shutdownhttps://support.industry.siemens.com/cs/de/en/view/39198632
Security
signed firmware updateNo
data integrityNo
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.70 °C; = Tmax; > +60 °C Number of simultaneously controllable outputs max. 8x 0.5 A, max. total current per group 2 A
vertical installation, min.-40 °C; = Tmin
vertical installation, max.40 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.240 g
Approvals / Certificates