6AG1521-7EH00-7AB0

6AG1521-7EH00-7AB0

SIPLUS S7-1500 DI 16x 48 V UC/ 125 V na bázi 6ES7521-7EH00-0AB0 s ochranným lakováním, -40…+70 °C, modul digitálních vstupů, 16 kanálů ve skupinách po 1; zpoždění vstupu 0.05..20 ms, typ vstupu 3 (IEC 61131); diagnostika; hardwarové přerušení.

Kategorie produktu
Digitální moduly
Výrobce
SIEMENS
Produktová řada
S7-1500
General information
Product type designationDI 16x24 ... 125 V UC HF
Firmware version
FW update possibleYes
based on6ES7521-7EH00-0AB0
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Prioritized startupYes
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
DIYes
CounterYes; from V1.1.0; only in DC operation
OversamplingNo
MSIYes
Power
Power consumption from the backplane bus1.2 W
Power loss
Power loss, typ.2.2 W; At 24 V DC; 6.0 W at 125 V AC
Digital inputs
Number of digital inputs16; > +60 °C number of simultaneously controllable inputs max. 4 (no adjacent points)
Digital inputs, parameterizableYes
Sourcing/sinking inputYes
Input characteristic curve in accordance with IEC 61131, type 3Yes; At 24 V DC
Digital input functions, parameterizable
CounterYes; from FS04
Number, max.2; Channel 0 and 1
Counting frequency, max.6 kHz
Counting width32 bit
Counting direction up/downYes; Up
Input voltage
Rated value (DC)24 V; 48 V, 125 V
Rated value (AC)24 V; 48 V, 125 V (50 - 60 Hz)
for signal "0"-5 ... +5 V
for signal "1"+11 ... +146 V
Input current
for signal "1", typ.3 mA; At 24 V DC
Input delay (for rated value of input voltage)
for standard inputs
parameterizableYes; 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms parameterizable with DC, 20 ms fixed with AC
at "0" to "1", min.0.05 ms
at "0" to "1", max.20 ms
at "1" to "0", min.0.05 ms
at "1" to "0", max.20 ms
for interrupt inputs
parameterizableYes
for technological functions
parameterizableNo
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Encoder
Connectable encoders
2-wire sensorYes
permissible quiescent current (2-wire sensor), max.1.5 mA
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Hardware interruptYes
Diagnoses
Monitoring the supply voltageNo
Wire breakYes; To I < 550 µA
Short-circuitNo
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
Monitoring of the supply voltage (PWR-LED)No
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; red LED
Potential separation
Potential separation channels
between the channelsYes
between the channels, in groups of1
between the channels and backplane busYes
Permissible potential difference
between different circuits146 V DC/132 V AC
Standards, approvals, certificates
Suitable for safety functionsNo
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]18.9 kg
global warming potential, (during production) [CO2 eq]12.1 kg
global warming potential, (during operation) [CO2 eq]7.66 kg
global warming potential, (after end of life cycle) [CO2 eq]-1.02 kg
Security
signed firmware updateYes
data integrityNo
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. 4 inputs (no adjacent points)
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.240 g
Approvals / Certificates