6AG1532-5HF00-7AB0
SIPLUS S7-1500 AQ 8xU/I HS na bázi 6ES7532-5HF00-0AB0 s ochranným lakováním, -40…+70 °C, náběh -25 °C, modul analogových výstupů, rozlišení 16 bitů, přesnost 0.4 %, 8 kanálů ve skupinách po 8, diagnostika; náhradní hodnota, 8 kanálů v 0.125 ms, včetně přívodního elementu, stínicího držáku a stínicí svorky.
Kategorie produktu
Analogové modulyVýrobce
SIEMENSProduktová řada
S7-1500| General information | |
|---|---|
| Product type designation | AQ 8xU/I HS |
| Firmware version | |
| FW update possible | Yes |
| based on | 6ES7532-5HF00-0AB0 |
| Product function | |
| I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | Yes |
| Prioritized startup | No |
| Output range scalable | No |
| Engineering with | |
| STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 |
| Operating mode | |
| Oversampling | Yes |
| MSO | Yes |
| CiR - Configuration in RUN | |
| Reparameterization possible in RUN | Yes |
| Calibration possible in RUN | Yes |
| Supply voltage | |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Input current | |
| Current consumption, max. | 320 mA; with 19.2 V supply |
| Power | |
| Power consumption from the backplane bus | 1.15 W |
| Power loss | |
| Power loss, typ. | 7 W |
| Analog outputs | |
| Number of analog outputs | 8; > +60 °C max. 4x ±10 V permissible |
| Voltage output, short-circuit protection | Yes |
| Voltage output, short-circuit current, max. | 45 mA |
| Current output, no-load voltage, max. | 20 V |
| Cycle time (all channels), min. | 125 µs; independent of number of activated channels |
| Output ranges, voltage | |
| 0 to 10 V | Yes |
| 1 V to 5 V | Yes |
| -5 V to +5 V | No |
| -10 V to +10 V | Yes |
| Output ranges, current | |
| 0 to 20 mA | Yes |
| -20 mA to +20 mA | Yes |
| 4 mA to 20 mA | Yes |
| Connection of actuators | |
| for voltage output two-wire connection | Yes |
| for voltage output four-wire connection | Yes |
| for current output two-wire connection | Yes |
| Load impedance (in rated range of output) | |
| with voltage outputs, min. | 1 kΩ |
| with voltage outputs, capacitive load, max. | 100 nF |
| with current outputs, max. | 500 Ω |
| with current outputs, inductive load, max. | 1 mH |
| Cable length | |
| shielded, max. | 200 m |
| Analog value generation for the outputs | |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 16 bit |
| Conversion time (per channel) | 50 µs; independent of number of activated channels |
| Settling time | |
| for resistive load | 30 µs; see additional description in the manual |
| for capacitive load | 100 µs; see additional description in the manual |
| for inductive load | 100 µs; see additional description in the manual |
| Errors/accuracies | |
| Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | 0.02 % |
| Linearity error (relative to output range), (+/-) | 0.15 % |
| Temperature error (relative to output range), (+/-) | 0.002 %/K |
| Crosstalk between the outputs, max. | -100 dB |
| Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % |
| note regarding accuracy | at temperatures below 0 °C, the figures for operating error and temperature error are doubled |
| Operational error limit in overall temperature range | |
| Voltage, relative to output range, (+/-) | 0.4 % |
| Current, relative to output range, (+/-) | 0.4 % |
| Basic error limit (operational limit at 25 °C) | |
| Voltage, relative to output range, (+/-) | 0.2 % |
| Current, relative to output range, (+/-) | 0.2 % |
| Isochronous mode | |
| Execution and activation time (TCO), min. | 100 µs |
| Bus cycle time (TDP), min. | 250 µs |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Alarms | |
| Diagnostic alarm | Yes |
| Diagnoses | |
| Monitoring the supply voltage | Yes |
| Wire break | Yes; Only for output type "current" |
| Short-circuit | Yes; Only for output type "voltage" |
| Overflow/Underflow | Yes |
| Diagnostics indication LED | |
| RUN LED | Yes; green LED |
| ERROR LED | Yes; red LED |
| Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
| Channel status display | Yes; green LED |
| for channel diagnostics | Yes; red LED |
| for module diagnostics | Yes; red LED |
| Potential separation | |
| Potential separation channels | |
| between the channels | No |
| between the channels, in groups of | 8 |
| between the channels and backplane bus | Yes |
| Between the channels and load voltage L+ | Yes |
| Permissible potential difference | |
| between S- and MANA (UCM) | 8 V DC |
| Isolation | |
| Isolation tested with | 707 V DC (type test) |
| Standards, approvals, certificates | |
| Suitable for safety-related tripping of standard modules | Yes; from FS04 |
| Ecological footprint | |
| environmental product declaration | Yes |
| Global warming potential | |
| global warming potential, (total) [CO2 eq] | 37.6 kg |
| global warming potential, (during production) [CO2 eq] | 11.1 kg |
| global warming potential, (during operation) [CO2 eq] | 26.8 kg |
| global warming potential, (after end of life cycle) [CO2 eq] | -0.364 kg |
| Highest safety class achievable for safety-related tripping of standard modules | |
| Performance level according to ISO 13849-1 | PL d |
| Category according to ISO 13849-1 | Cat. 3 |
| SIL acc. to IEC 62061 | SIL 2 |
| remark on safety-oriented shutdown | https://support.industry.siemens.com/cs/de/en/view/39198632 |
| Security | |
| signed firmware update | No |
| data integrity | No |
| Ambient conditions | |
| Ambient temperature during operation | |
| horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C |
| horizontal installation, max. | 70 °C; = Tmax; > +60 °C max. 4x ±10 V permissible |
| vertical installation, min. | -40 °C; = Tmin; Startup @ -25 °C |
| vertical installation, max. | 40 °C; = Tmax |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m |
| Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
| Relative humidity | |
| With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Resistance | |
| Coolants and lubricants | |
| Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air |
| Use in stationary industrial systems | |
| to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
| Use on ships/at sea | |
| to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
| to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
| Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
| Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| Conformal coating | |
| Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability |
| Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
| Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
| Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A |
| Dimensions | |
| Width | 35 mm |
| Height | 147 mm |
| Depth | 129 mm |
| Weights | |
| Weight, approx. | 325 g |
| Approvals / Certificates | |