6AG1222-1HF32-2XB0

6AG1222-1HF32-2XB0

SIPLUS S7-1200 SM 1222 8DQ RLY na bázi 6ES7222-1HF32-0XB0 s ochranným lakováním, -40…+70 °C, náběh -25 °C, digitální výstup 8 DQ, relé 2 A.

Kategorie produktu
Signal modules
Výrobce
SIEMENS
Produktová řada
S7-1200
General information
Product type designationSM 1222, DQ 8x relay/2 A
based on6ES7222-1HF32-0XB0
Supply voltage
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
from backplane bus 5 V DC, max.120 mA
Digital outputs
from load voltage L+, max.11 mA/relay coil
Power loss
Power loss, typ.4.5 W
Digital outputs
Number of digital outputs8
in groups of2
Short-circuit protectionNo; to be provided externally
Switching capacity of the outputs
with resistive load, max.2 A
on lamp load, max.30 W with DC, 200 W with AC
Output voltage
Rated value (DC)5 V DC to 30 V DC
Rated value (AC)5 V AC to 250 V AC
Output current
for signal "1" rated value2 A
Output delay with resistive load
"0" to "1", max.10 ms
"1" to "0", max.10 ms
Total current of the outputs (per group)
horizontal installation
up to 50 °C, max.10 A; Current per mass
Relay outputs
Number of relay outputs8
Rated supply voltage of relay coil L+ (DC)24 V
Number of operating cycles, max.mechanically 10 million, at rated load voltage 100 000
Switching capacity of contacts
with inductive load, max.2 A
on lamp load, max.30 W with DC, 200 W with AC
with resistive load, max.2 A
Cable length
shielded, max.500 m
unshielded, max.150 m
Interrupts/diagnostics/status information
Alarms
Diagnostic alarmYes
Diagnostics indication LED
for status of the outputsYes
Potential separation
Potential separation digital outputs
between the channelsRelays
between the channels, in groups of2
between the channels and backplane bus1 500 V AC for 1 minute
Permissible potential difference
between different circuits750 V AC for 1 minute
Degree and class of protection
IP degree of protectionIP20
Standards, approvals, certificates
Ecological footprint
environmental product declarationYes
Global warming potential
global warming potential, (total) [CO2 eq]68.6 kg
global warming potential, (during production) [CO2 eq]8.16 kg
global warming potential, (during operation) [CO2 eq]60.7 kg
global warming potential, (after end of life cycle) [CO2 eq]-0.334 kg
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
max.70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 4 (no adjacent points) for horizontal mounting position
At cold restart, min.-25 °C
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m); above 2 000 m max. 132 V AC
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Connection method
required front connectorYes
Mechanics/material
Enclosure material (front)
PlasticYes
Dimensions
Width45 mm
Height100 mm
Depth75 mm
Weights
Weight, approx.190 g
Approvals / Certificates