6ES7231-5PA30-0XB0

6ES7231-5PA30-0XB0

SIMATIC S7-1200, analogový vstup, SB 1231RTD, 1 AI RTD, Pt100 a Pt1000.

Kategorie produktu
Signal boards
Výrobce
SIEMENS
Produktová řada
S7-1200
General information
Product type designationSB 1231, AI 1x16 bit RTD
Supply voltage
Rated value (DC)24 V
Input current
Current consumption, typ.5 mA
from backplane bus 5 V DC, typ.20 mA
Power loss
Power loss, typ.0.5 W
Analog inputs
Number of analog inputs1; Resistance thermometer
permissible input voltage for current input (destruction limit), max.±35 V
Technical unit for temperature measurement adjustableDegrees Celsius/degrees Fahrenheit
Input ranges
VoltageYes
CurrentNo
ThermocoupleNo
Resistance thermometerYes; Platinum (Pt)
ResistanceYes; 150 Ω, 300 Ω, 600 Ω
Input ranges (rated values), voltages
-80 mV to +80 mV
Input resistance (-80 mV to +80 mV)>= 10 MOhm
Input ranges (rated values), resistance thermometer
Pt 100Yes
Input resistance (Pt 100)100 Ω
Pt 1000Yes
Input resistance (Pt 1000)1 000 Ω
Pt 200Yes
Input resistance (Pt 200)200 Ω
Pt 500Yes
Input resistance (Pt 500)500 Ω
Input ranges (rated values), resistors
0 to 150 ohmsYes
0 to 300 ohmsYes
0 to 600 ohmsYes
Thermocouple (TC)
Temperature compensation
ParameterizableNo
Analog outputs
Number of analog outputs0
Cable length
shielded, max.100 m; shielded, twisted pair
Analog value generation for the inputs
Measurement principleintegrating
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.15 bit; + sign
Integration time, parameterizableNo
Interference voltage suppression for interference frequency f1 in Hz85 dB at 10 / 50 / 60 / 400 Hz
Errors/accuracies
Temperature error (relative to input range), (+/-)25 °C ±0.1%, to 55 °C ±0.2% total measurement range
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.05 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Common mode interference, min.120 dB
Interrupts/diagnostics/status information
AlarmsYes
Diagnostics functionYes; Can be read out
Alarms
Diagnostic alarmYes
Diagnoses
Wire breakYes
Diagnostics indication LED
for status of the inputsYes
for maintenanceYes
Standards, approvals, certificates
CE markYes
CSA approvalYes
UL approvalYes
cULusYes
FM approvalYes
RCM (formerly C-TICK)Yes
KC approvalYes
Marine approvalYes
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.-20 °C
max.60 °C
horizontal installation, min.-20 °C
horizontal installation, max.60 °C
vertical installation, min.-20 °C
vertical installation, max.50 °C
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Air pressure acc. to IEC 60068-2-13
Operation, min.795 hPa
Operation, max.1 080 hPa
Storage/transport, min.660 hPa
Storage/transport, max.1 080 hPa
Relative humidity
Operation at 25 ℃ without condensation, max.95 %
Pollutant concentrations
SO2 at RH < 60% without condensationS02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free
Connection method
required front connectorYes
Mechanics/material
Enclosure material (front)
PlasticYes
Dimensions
Width38 mm
Height62 mm
Depth21 mm
Weights
Weight, approx.35 g
Approvals / Certificates