6ES7322-5HF00-0AB0
Kategorie produktu
Digitální modulyVýrobce
SIEMENSProduktová řada
S7-300| Supply voltage | |
|---|---|
| Load voltage L+ | |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 24 V |
| permissible range, upper limit (DC) | 120 V |
| Load voltage L1 | |
| Rated value (AC) | 230 V |
| Input current | |
| from supply voltage L+, max. | 160 mA |
| from backplane bus 5 V DC, max. | 100 mA |
| Power loss | |
| Power loss, typ. | 3.5 W |
| Digital outputs | |
| Number of digital outputs | 8; Relays |
| Short-circuit protection | No; to be provided externally |
| Controlling a digital input | Yes |
| Switching capacity of the outputs | |
| on lamp load, max. | 1 500 W; 230 V AC |
| Low energy/fluorescent lamps with electronic control gear | 10x 58 W |
| Fluorescent tubes, conventionally compensated | 1x 58 W |
| Fluorescent tubes, uncompensated | 10x 58 W |
| Output current | |
| for signal "1" rated value | 5 A |
| for signal "1" minimum load current | 10 mA |
| Parallel switching of two outputs | |
| for uprating | No |
| for redundant control of a load | Yes |
| Switching frequency | |
| with resistive load, max. | 2 Hz |
| with inductive load, max. | 0.5 Hz |
| With inductive load (to IEC 60947-5-1, DC13/AC15), max. | 0.5 Hz |
| on lamp load, max. | 2 Hz |
| mechanical, max. | 10 Hz |
| Total current of the outputs (per group) | |
| horizontal installation | |
| up to 60 °C, max. | 5 A |
| vertical installation | |
| up to 40 °C, max. | 5 A |
| Relay outputs | |
| Contact connection (internal) | Yes; 330 Ohm, 0.1uF |
| Number of operating cycles, max. | 100 000; 100 000 (24 V DC, at 5 A), 100 000 (230 V AC, at 5 A) |
| Switching capacity of contacts | |
| with inductive load, max. | 5 A; 5 A (230 V DC), 5 A (24 V AC) |
| with resistive load, max. | 5 A; 5 A (230 V DC), 5 A (24 V AC) |
| Thermal continuous current, max. | 5 A |
| Cable length | |
| shielded, max. | 1 000 m |
| unshielded, max. | 600 m |
| Interrupts/diagnostics/status information | |
| Alarms | Yes |
| Diagnostics function | Yes; Parameterizable |
| Alarms | |
| Diagnostic alarm | Yes; Parameterizable |
| Diagnoses | |
| Diagnostic information readable | Yes |
| Diagnostics indication LED | |
| Group error SF (red) | Yes |
| Status indicator digital output (green) | Yes |
| Potential separation | |
| Potential separation digital outputs | |
| between the channels | Yes |
| between the channels, in groups of | 1 |
| between the channels and backplane bus | Yes; Optocoupler |
| Between the channels and the power supply of the relays | Yes |
| Isolation | |
| Isolation tested with | 1 500 V AC |
| Connection method | |
| required front connector | 40-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights | |
| Weight, approx. | 320 g |
| Approvals / Certificates | |