6AG1332-7ND02-4AB0
SIPLUS S7-300 SM 332 4 AO based on 6ES7332-7ND02-0AB0 with conformal coating, 0…+60 °C, analog output isolated by channel, 4 AO, resolution 16 bit, 0-10 V, 1-5 V, +/-10 V, +/-20 mA, 0/4-20 mA, 20-pole, suitable for isochronous mode improved bus cycle times for the isochronous mode
Siemens spare part — S7-300 product cancellation (PM410, 1 October 2025); available as a spare part until 2033.
Kategorie produktu
Analogové modulyVýrobce
SIEMENSProduktová řada
S7-300| General information | |
|---|---|
| based on | 6ES7332-7ND02-0AB0 |
| Product function | |
| Isochronous mode | Yes |
| Supply voltage | |
| Load voltage L+ | |
| Rated value (DC) | 24 V |
| Reverse polarity protection | Yes |
| Input current | |
| from load voltage L+ (without load), max. | 290 mA |
| from backplane bus 5 V DC, max. | 120 mA |
| Power loss | |
| Power loss, typ. | 3 W |
| Analog outputs | |
| Number of analog outputs | 4; Isochronous mode |
| Voltage output, short-circuit protection | Yes |
| Voltage output, short-circuit current, max. | 40 mA |
| Current output, no-load voltage, max. | 18 V |
| Output ranges, voltage | |
| 0 to 10 V | Yes |
| 1 V to 5 V | Yes |
| -10 V to +10 V | Yes |
| Output ranges, current | |
| 0 to 20 mA | Yes |
| -20 mA to +20 mA | Yes |
| 4 mA to 20 mA | Yes |
| Connection of actuators | |
| for voltage output four-wire connection | Yes |
| for current output two-wire connection | Yes |
| Load impedance (in rated range of output) | |
| with voltage outputs, min. | 1 kΩ |
| with voltage outputs, capacitive load, max. | 1 µF |
| with current outputs, max. | 500 Ω |
| with current outputs, inductive load, max. | 1 mH |
| Cable length | |
| shielded, max. | 200 m |
| Analog value generation for the outputs | |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 16 bit |
| Conversion time (per channel) | 200 µs; in isochronous mode 640 µs |
| Settling time | |
| for resistive load | 0.2 ms |
| for capacitive load | 3.3 ms |
| for inductive load | 0.5 ms |
| Errors/accuracies | |
| Operational error limit in overall temperature range | |
| Voltage, relative to output range, (+/-) | 0.12 % |
| Current, relative to output range, (+/-) | 0.18 % |
| Basic error limit (operational limit at 25 °C) | |
| Voltage, relative to output range, (+/-) | 0.02 % |
| Current, relative to output range, (+/-) | 0.02 % |
| Interrupts/diagnostics/status information | |
| Substitute values connectable | Yes; Parameterizable |
| Alarms | |
| Diagnostic alarm | Yes |
| Diagnostics indication LED | |
| Group error SF (red) | Yes |
| Potential separation | |
| Potential separation analog outputs | |
| between the channels | Yes |
| between the channels and backplane bus | Yes |
| between the channels and the power supply of the electronics | Yes |
| Isolation | |
| Isolation tested with | 1 500 V DC |
| Standards, approvals, certificates | |
| CE mark | Yes |
| UL approval | Yes; File E239877 |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| EAC (formerly Gost-R) | Yes |
| Ambient conditions | |
| Ambient temperature during operation | |
| min. | 0 °C; = Tmin |
| max. | 60 °C; = Tmax |
| Ambient temperature during storage/transportation | |
| min. | -40 °C |
| max. | 70 °C |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m |
| Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
| Relative humidity | |
| With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Resistance | |
| Use in stationary industrial systems | |
| to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
| Use on ships/at sea | |
| to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
| to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
| Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
| Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| Connection method | |
| required front connector | 20-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights | |
| Weight, approx. | 220 g |
| Approvals / Certificates | |