6ES7522-1BP00-0AA0
SIMATIC S7-1500, modul digitálních výstupů, DQ 64xDC 24V/0,3A BA, 64 kanálů ve skupinách po 16, 2 A na skupinu při 60 °C, sinking výstup, šířka 35 mm, modul podporuje bezpečnostní vypnutí zátěžových skupin až do SIL2 podle EN IEC 62061:2021 a kategorie 3 / PL d podle EN ISO 13849-1:2015. Kabely a svorkovnice se objednávají samostatně jako příslušenství.
Kategorie produktu
Digitální modulyVýrobce
SIEMENSProduktová řada
S7-1500| General information | |
|---|---|
| Product type designation | DQ 64x24VDC/0.3A BA |
| HW functional status | from FS01 |
| Firmware version | V1.0.0 |
| FW update possible | Yes |
| Product function | |
| I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | No |
| Prioritized startup | No |
| Engineering with | |
| STEP 7 TIA Portal configurable/integrated from version | V16 with HSP 0319 / V17 |
| STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| PROFINET from GSD version/GSD revision | V2.35 / - |
| Operating mode | |
| DQ | Yes |
| DQ with energy-saving function | No |
| PWM | No |
| Cam control (switching at comparison values) | No |
| Oversampling | No |
| MSO | Yes |
| Integrated operating cycle counter | No |
| Supply voltage | |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes; through internal protection with 7 A per group |
| external protection for power supply lines (recommendation) | 24 V DC/6 A miniature circuit breaker with type B tripping characteristic |
| Input current | |
| Current consumption, max. | 90 mA; without load |
| Output voltage | |
| Rated value (DC) | 24 V |
| Power | |
| Power consumption from the backplane bus | 0.6 W |
| Power loss | |
| Power loss, typ. | 3.5 W |
| Address area | |
| Address space per module | |
| Inputs | 0 byte; typical, maximum 56 bytes, see manual for details |
| Outputs | 8 byte |
| Digital outputs | |
| Type of digital output | Transistor |
| Number of digital outputs | 64 |
| Current-sinking | No |
| Current-sourcing | Yes |
| Digital outputs, parameterizable | No |
| Short-circuit protection | Yes |
| Limitation of inductive shutdown voltage to | L+ (-53 V) |
| Controlling a digital input | Yes |
| Digital output functions, parameterizable | |
| Switching tripped by comparison values | No |
| Freely usable digital output | No |
| PWM output | No |
| Digital output with oversampling | No |
| Switching capacity of the outputs | |
| with resistive load, max. | 0.3 A |
| on lamp load, max. | 5 W |
| Load resistance range | |
| lower limit | 80 Ω |
| upper limit | 10 kΩ |
| Output voltage | |
| for signal "1", min. | L+ (-0.8 V) |
| Output current | |
| for signal "1" rated value | 0.3 A |
| for signal "1" permissible range, max. | 0.3 A |
| for signal "0" residual current, max. | 0.5 mA |
| Output delay with resistive load | |
| "0" to "1", max. | 100 µs |
| "1" to "0", max. | 500 µs |
| Parallel switching of two outputs | |
| for logic links | Yes |
| for uprating | No |
| for redundant control of a load | Yes |
| Switching frequency | |
| with resistive load, max. | 100 Hz |
| with inductive load, max. | 0.5 Hz; According to IEC 60947-5-1, DC-13 |
| on lamp load, max. | 10 Hz |
| Total current of the outputs | |
| Current per channel, max. | 0.3 A |
| Current per group, max. | 2 A |
| Current per module, max. | 8 A |
| Cable length | |
| shielded, max. | 1 000 m |
| unshielded, max. | 600 m |
| Interrupts/diagnostics/status information | |
| Diagnostics function | No |
| Substitute values connectable | No |
| Alarms | |
| Diagnostic alarm | No |
| Maintenance interrupt | No |
| Diagnoses | |
| Monitoring the supply voltage | No |
| Wire break | No |
| short-circuit | No |
| Group error | No |
| Diagnostics indication LED | |
| RUN LED | Yes; green LED |
| ERROR LED | Yes; red LED |
| MAINT LED | No |
| Monitoring of the supply voltage (PWR-LED) | Yes; via SIMATIC TOP connect connection module |
| Channel status display | Yes; via SIMATIC TOP connect connection module |
| for channel diagnostics | No |
| for module diagnostics | No |
| Potential separation | |
| Potential separation channels | |
| between the channels | No |
| between the channels, in groups of | 16; 32 when using SIMATIC TOP connect connection module |
| between the channels and backplane bus | Yes |
| Isolation | |
| Isolation tested with | 707 V DC (type test) |
| Standards, approvals, certificates | |
| Siemens Eco Profile (SEP) | Siemens EcoTech |
| Suitable for safety functions | No |
| Suitable for safety-related tripping of standard modules | Yes; from FS01 |
| Ecological footprint | |
| environmental product declaration | Yes |
| Global warming potential | |
| global warming potential, (total) [CO2 eq] | 43.8 kg |
| global warming potential, (during production) [CO2 eq] | 9.5 kg |
| global warming potential, (during operation) [CO2 eq] | 34.5 kg |
| global warming potential, (after end of life cycle) [CO2 eq] | -0.231 kg |
| Highest safety class achievable for safety-related tripping of standard modules | |
| Performance level according to ISO 13849-1 | PL d |
| Category according to ISO 13849-1 | Cat. 3 |
| SIL acc. to IEC 62061 | SIL 2 |
| remark on safety-oriented shutdown | https://support.industry.siemens.com/cs/de/en/view/39198632 |
| Security | |
| safely removing data | No |
| Ambient conditions | |
| Ambient temperature during operation | |
| horizontal installation, min. | -30 °C |
| horizontal installation, max. | 60 °C |
| vertical installation, min. | -30 °C |
| vertical installation, max. | 40 °C |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m |
| Absolute humidity | |
| dew point, min. | -60 °C; suitable for dry room applications |
| Dimensions | |
| Width | 35 mm |
| Height | 147 mm |
| Depth | 129 mm |
| Weights | |
| Weight, approx. | 270 g |
| Other | |
| Note: | Please order cable and connection modules separately |
| Approvals / Certificates | |