6ES7553-1AA01-0AB0

6ES7553-1AA01-0AB0

SIMATIC S7-1500, TM PTO 4, модуль інтерфейсу для крокових приводів, 4 канали виходу імпульсного сигналу PTO: 24 В, RS-422, 5 В, 2 DI, 1 DQ 24 В DC на канал.

Категорія товару
Технологічні модулі
Виробник
SIEMENS
Серія продуктів
S7-1500
General information
Product type designationTM PTO 4
Number of channels4; Axes
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeYes
Engineering with
STEP 7 TIA Portal configurable/integrated from versionSTEP 7 V19 or higher
STEP 7 configurable/integrated from versionV5.5 SP3 with GSD file / -
PROFINET from GSD version/GSD revisionGSDML V2.43
Installation type/mounting
Rail mountingYes; S7-1500 mounting rail
Supply voltage
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.70 mA; without load
Power
Power consumption from the backplane bus1.3 W
Power loss
Power loss, typ.4 W
Address area
Address space per module
Inputs72 byte; 18 per channel
Outputs40 byte; 10 per channel
Digital inputs
Number of digital inputs12; 3 per channel, of which 1 DIQ
Digital inputs, parameterizableYes
Input characteristic curve in accordance with IEC 61131, type 3Yes
Digital input functions, parameterizable
SynchronizationYes
ProbeYes
Drive readyYes
Input voltage
Type of input voltageDC
Rated value (DC)24 V
for signal "0"-5 ... +5 V
for signal "1"+11 to +30V
permissible voltage at input, min.-5 V
permissible voltage at input, max.30 V
Input current
for signal "1", typ.2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizableYes; none / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms
for technological functions
ParameterizableYes
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Digital outputs
Number of digital outputs12; 3 per channel, of which 1 DIQ
Current-sinkingYes; For DQn.0 and DQn.1 push-pull outputs
Current-sourcingYes
Digital outputs, parameterizableYes
Short-circuit protectionYes; electronic/thermal
Response threshold, typ.0.2 A for DQn.0 and DQn.1, 0.9 A for DIQn.2
Controlling a digital inputYes
Digital output functions, parameterizable
PTO (pulse train output) signal interface
24 V asymmetricalYes
RS 422 symmetricalYes
TTL (5 V) asymmetricalYes
PTO (pulse train output) signal type
Pulse and directionYes
Count up, count downYes
Incremental encoder (A, B phase shift)Yes
Incremental encoder (A, B phase shift, quadruple)Yes
Switching capacity of the outputs
with resistive load, max.0.1 A; 0.5 A for DIQn.2
Load resistance range
lower limit240 Ω; 48 ohms for DIQn.2
upper limit12 kΩ
Output voltage
Type of output voltageDC
for signal "1", min.23.2 V; L+ (-0.8 V), L+ (-1.3 V) for DIQn.2
Output current
for signal "1" rated value0.1 A; 0.5 A for DIQn.2
for signal "1" permissible range, max.0.12 A; 0.6 A for DIQn.2
for signal "1" minimum load current2 mA
for signal "0" residual current, max.0.5 mA
Output delay with resistive load
"0" to "1", typ.1 µs; 28 µs for DIQn.2
"1" to "0", typ.1 µs; 25 µs for DIQn.2
Switching frequency
with resistive load, max.1 kHz; For DIQn.2
with inductive load, max.0.5 Hz; According to IEC 60947-5-1, DC-13, for DIQn.2
For signal interface 24 V asymmetrical200 kHz; With DQn.0 and DQn.1
For signal interface RS 422 symmetrical1 MHz
For signal interface TTL (5 V) asymmetrical200 kHz
Cable length
shielded, max.600 m; 600 m for technological functions; depending on output frequency, load, and cable quality
Isochronous mode
Bus cycle time (TDP), min.250 µs; 375 µs if all 4 channels are used
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Diagnoses
Monitoring the supply voltageYes
short-circuitYes; Thermal overload protection
Group errorYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
MAINT LEDYes; Yellow LED
Monitoring of the supply voltage (PWR-LED)Yes; green LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
Potential separation
Potential separation channels
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+No
Isolation
Isolation tested with707 V DC (type test)
Security
signed firmware updateYes
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-30 °C
horizontal installation, max.60 °C; Observe derating
vertical installation, min.-30 °C
vertical installation, max.40 °C; Observe derating
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200MP system manual
Absolute humidity
dew point, min.-60 °C; suitable for dry room applications
Decentralized operation
to SIMATIC S7-300Yes; Via control and feedback interface
to SIMATIC S7-400Yes; Via control and feedback interface
to SIMATIC S7-1200Yes
to SIMATIC S7-1500Yes
to standard PROFINET controllerYes; Via control and feedback interface
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.300 g
Approvals / Certificates