6ES7553-1AA01-0AB0
SIMATIC S7-1500, TM PTO 4, модуль інтерфейсу для крокових приводів, 4 канали виходу імпульсного сигналу PTO: 24 В, RS-422, 5 В, 2 DI, 1 DQ 24 В DC на канал.
Категорія товару
Технологічні модуліВиробник
SIEMENSСерія продуктів
S7-1500| General information | |
|---|---|
| Product type designation | TM PTO 4 |
| Number of channels | 4; Axes |
| Product function | |
| I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | Yes |
| Engineering with | |
| STEP 7 TIA Portal configurable/integrated from version | STEP 7 V19 or higher |
| STEP 7 configurable/integrated from version | V5.5 SP3 with GSD file / - |
| PROFINET from GSD version/GSD revision | GSDML V2.43 |
| Installation type/mounting | |
| Rail mounting | Yes; S7-1500 mounting rail |
| Supply voltage | |
| Load voltage L+ | |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Input current | |
| Current consumption, max. | 70 mA; without load |
| Power | |
| Power consumption from the backplane bus | 1.3 W |
| Power loss | |
| Power loss, typ. | 4 W |
| Address area | |
| Address space per module | |
| Inputs | 72 byte; 18 per channel |
| Outputs | 40 byte; 10 per channel |
| Digital inputs | |
| Number of digital inputs | 12; 3 per channel, of which 1 DIQ |
| Digital inputs, parameterizable | Yes |
| Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
| Digital input functions, parameterizable | |
| Synchronization | Yes |
| Probe | Yes |
| Drive ready | Yes |
| Input voltage | |
| Type of input voltage | DC |
| Rated value (DC) | 24 V |
| for signal "0" | -5 ... +5 V |
| for signal "1" | +11 to +30V |
| permissible voltage at input, min. | -5 V |
| permissible voltage at input, max. | 30 V |
| Input current | |
| for signal "1", typ. | 2.5 mA |
| Input delay (for rated value of input voltage) | |
| for standard inputs | |
| parameterizable | Yes; none / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms |
| for technological functions | |
| Parameterizable | Yes |
| Cable length | |
| shielded, max. | 1 000 m |
| unshielded, max. | 600 m |
| Digital outputs | |
| Number of digital outputs | 12; 3 per channel, of which 1 DIQ |
| Current-sinking | Yes; For DQn.0 and DQn.1 push-pull outputs |
| Current-sourcing | Yes |
| Digital outputs, parameterizable | Yes |
| Short-circuit protection | Yes; electronic/thermal |
| Response threshold, typ. | 0.2 A for DQn.0 and DQn.1, 0.9 A for DIQn.2 |
| Controlling a digital input | Yes |
| Digital output functions, parameterizable | |
| PTO (pulse train output) signal interface | |
| 24 V asymmetrical | Yes |
| RS 422 symmetrical | Yes |
| TTL (5 V) asymmetrical | Yes |
| PTO (pulse train output) signal type | |
| Pulse and direction | Yes |
| Count up, count down | Yes |
| Incremental encoder (A, B phase shift) | Yes |
| Incremental encoder (A, B phase shift, quadruple) | Yes |
| Switching capacity of the outputs | |
| with resistive load, max. | 0.1 A; 0.5 A for DIQn.2 |
| Load resistance range | |
| lower limit | 240 Ω; 48 ohms for DIQn.2 |
| upper limit | 12 kΩ |
| Output voltage | |
| Type of output voltage | DC |
| for signal "1", min. | 23.2 V; L+ (-0.8 V), L+ (-1.3 V) for DIQn.2 |
| Output current | |
| for signal "1" rated value | 0.1 A; 0.5 A for DIQn.2 |
| for signal "1" permissible range, max. | 0.12 A; 0.6 A for DIQn.2 |
| for signal "1" minimum load current | 2 mA |
| for signal "0" residual current, max. | 0.5 mA |
| Output delay with resistive load | |
| "0" to "1", typ. | 1 µs; 28 µs for DIQn.2 |
| "1" to "0", typ. | 1 µs; 25 µs for DIQn.2 |
| Switching frequency | |
| with resistive load, max. | 1 kHz; For DIQn.2 |
| with inductive load, max. | 0.5 Hz; According to IEC 60947-5-1, DC-13, for DIQn.2 |
| For signal interface 24 V asymmetrical | 200 kHz; With DQn.0 and DQn.1 |
| For signal interface RS 422 symmetrical | 1 MHz |
| For signal interface TTL (5 V) asymmetrical | 200 kHz |
| Cable length | |
| shielded, max. | 600 m; 600 m for technological functions; depending on output frequency, load, and cable quality |
| Isochronous mode | |
| Bus cycle time (TDP), min. | 250 µs; 375 µs if all 4 channels are used |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Alarms | |
| Diagnostic alarm | Yes |
| Diagnoses | |
| Monitoring the supply voltage | Yes |
| short-circuit | Yes; Thermal overload protection |
| Group error | Yes |
| Diagnostics indication LED | |
| RUN LED | Yes; green LED |
| ERROR LED | Yes; red LED |
| MAINT LED | Yes; Yellow LED |
| Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
| Channel status display | Yes; green LED |
| for channel diagnostics | Yes; red LED |
| Potential separation | |
| Potential separation channels | |
| between the channels | No |
| between the channels and backplane bus | Yes |
| Between the channels and load voltage L+ | No |
| Isolation | |
| Isolation tested with | 707 V DC (type test) |
| Security | |
| signed firmware update | Yes |
| Ambient conditions | |
| Ambient temperature during operation | |
| horizontal installation, min. | -30 °C |
| horizontal installation, max. | 60 °C; Observe derating |
| vertical installation, min. | -30 °C |
| vertical installation, max. | 40 °C; Observe derating |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200MP system manual |
| Absolute humidity | |
| dew point, min. | -60 °C; suitable for dry room applications |
| Decentralized operation | |
| to SIMATIC S7-300 | Yes; Via control and feedback interface |
| to SIMATIC S7-400 | Yes; Via control and feedback interface |
| to SIMATIC S7-1200 | Yes |
| to SIMATIC S7-1500 | Yes |
| to standard PROFINET controller | Yes; Via control and feedback interface |
| Dimensions | |
| Width | 35 mm |
| Height | 147 mm |
| Depth | 129 mm |
| Weights | |
| Weight, approx. | 300 g |
| Approvals / Certificates | |