6AG1526-1BH00-2AB0

6AG1526-1BH00-2AB0

SIPLUS S7-1500 F-DI 16x24 V DC на основі 6ES7526-1BH00-0AB0 із захисним лакуванням, -30…+60 °C, модуль цифрових входів безпеки (F), загальна ширина 35 мм; до рівня PL E (ISO13849-1)/ SIL 3 (IEC 61508).

Категорія товару
Цифрові модулі
Виробник
SIEMENS
Серія продуктів
S7-1500
General information
Product type designationF-DI 16x24VDC
Firmware version
FW update possibleYes
based on6ES7526-1BH00-0AB0
Product function
I&M dataYes; I&M0 to I&M3
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
DIYes
MSINo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)50 mA; without load
Current consumption, max.60 mA; without load
Encoder supply
Number of outputs4
Short-circuit protectionYes; Electronic (response threshold 0.7 A to 1.8 A)
24 V encoder supply
24 VYes; min. L+ (-1.5 V)
Short-circuit protectionYes
Output current, max.300 mA; Max. 100 mA when mounted vertically
Power
Power consumption from the backplane bus0.9 W
Power loss
Power loss, typ.4.6 W
Address area
Address space per module
Inputs9 byte; S7-300/400F CPU, 8 byte
Outputs5 byte; S7-300/400F CPU, 4 byte
Hardware configuration
Automatic encodingYes
Electronic coding element type FYes
Digital inputs
Number of digital inputs16
Sourcing/sinking inputYes; P-reading
Input characteristic curve in accordance with IEC 61131, type 1Yes
Input voltage
Rated value (DC)24 V
for signal "0"-30 to +5 V
for signal "1"+15 to +30 V
Input current
for signal "1", typ.3.7 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizableYes
at "0" to "1", min.0.4 ms
at "0" to "1", max.20 ms
at "1" to "0", min.0.4 ms
at "1" to "0", max.20 ms
Cable length
shielded, max.1 000 m
unshielded, max.500 m
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Hardware interruptNo
Diagnoses
Monitoring the supply voltageYes
Wire breakNo
Short-circuitYes
Group errorYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; red LED
Potential separation
Potential separation channels
between the channels and backplane busYes
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functionsYes
Highest safety class achievable in safety mode
Performance level according to ISO 13849-1PLe
SIL acc. to IEC 61508SIL 3
Probability of failure (for service life of 20 years and repair time of 100 hours)
Low demand mode: PFDavg in accordance with SIL3< 5.00E-05
High demand/continuous mode: PFH in accordance with SIL3< 1.00E-09 1/h
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-30 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.60 °C; = Tmax
vertical installation, min.-30 °C; = Tmin
vertical installation, max.40 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Coolants and lubricants
Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.280 g
Approvals / Certificates