6ES7226-6BA32-0XB0

6ES7226-6BA32-0XB0

SIMATIC S7-1200, цифровий вхід SM 1226, F-DI 16x 24 В DC, PROFIsafe, загальна ширина 70 мм, до рівня PL E (ISO 13849-1)/ SIL3 (IEC 61508).

Категорія товару
Signal modules
Виробник
SIEMENS
Серія продуктів
S7-1200
General information
Product type designationSM 1226, F-DI 16x24 V DC
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
power supply according to NEC Class 2 requiredNo
Input current
from backplane bus 5 V DC, max.155 mA; Current consumption (SM Bus, 5 V DC): 155 mA
Digital inputs
from load voltage L+ (without load), max.130 mA; 130 mA + 6 mA / input used + any Vs1/Vs2 current used
Power loss
Power loss, typ.7 W
Digital inputs
Number of digital inputs16; 16 (1oo1) or 8 (1oo2); Note: You can individually assign each pair of inputs "a.x" and "b.x" as a single (1oo2)-channel or as 2 separate (1oo1)-channels
Number of simultaneously controllable inputs
horizontal installation
up to 50 °C, max.16; 16 inputs at 55 °C horizontal
vertical installation
up to 40 °C, max.16; 16 inputs at 45 °C vertical
Input voltage
for signal "0"-30 V DC to +5 V DC
for signal "1"15 V DC to 30 V DC
Input current
for signal "0", max. (permissible quiescent current)0.5 mA
for signal "1", typ.5 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizableYes; 0.8 / 1.6 / 3.2 / 6.4 / 12.8 ms
Cable length
shielded, max.200 m; unshielded with input filter time of 1.6 ms to 12.6 ms (With an input delay of 0.8 ms, shielded cables must be used for the digital inputs and the sensor supply)
unshielded, max.200 m; Shielded with input filter time of 0.8 ms to 12.6 s (With an input delay of 0.8 ms, shielded cables must be used for the digital inputs and the sensor supply)
Interrupts/diagnostics/status information
Diagnostics indication LED
for status of the inputsYes
Degree and class of protection
IP degree of protectionIP20
Standards, approvals, certificates
CE markYes
cULusYes
FM approvalYes
Highest safety class achievable in safety mode
Performance level according to ISO 13849-11-channel, Category 3, PL d; 2-channel, Category 3 or 4, PL e
SIL acc. to IEC 61508SIL 2 (single-channel), SIL 3 (two-channel)
Probability of failure (for service life of 20 years and repair time of 100 hours)
Low demand mode: PFDavg in accordance with SIL2< 5.00E-04
Low demand mode: PFDavg in accordance with SIL3< 1.00E-05
High demand/continuous mode: PFH in accordance with SIL2< 1.00E-08 1/h
High demand/continuous mode: PFH in accordance with SIL3< 1.00E-10 1/h
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.0 °C
max.55 °C
permissible temperature change5°C to 55°C, 3°C / minute
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Air pressure acc. to IEC 60068-2-13
Storage/transport, min.660 hPa
Storage/transport, max.1 080 hPa
Relative humidity
Operation at 25 ℃ without condensation, max.95 %
Mechanics/material
Enclosure material (front)
plasticYes
Dimensions
Width70 mm
Height100 mm
Depth75 mm
Weights
Weight, approx.250 g
Approvals / Certificates