6AG1222-1BH32-4XB0
SIPLUS S7-1200 SM 1222 16DQ на основі 6ES7222-1BH32-0XB0 із захисним лакуванням, -20…+60 °C, цифровий вихід 16 DQ, 24 В DC, транзисторний 0.5 А.
Категорія товару
Signal modulesВиробник
SIEMENSСерія продуктів
S7-1200| General information | |
|---|---|
| Product type designation | SM 1222, DQ 16x24 V DC/0.5 A |
| based on | 6ES7222-1BH32-0XB0 |
| Supply voltage | |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Input current | |
| from backplane bus 5 V DC, max. | 140 mA |
| Power loss | |
| Power loss, typ. | 2.5 W |
| Digital outputs | |
| Number of digital outputs | 16 |
| in groups of | 1 |
| Short-circuit protection | No; to be provided externally |
| Limitation of inductive shutdown voltage to | typ. (L+) -48 V |
| Switching capacity of the outputs | |
| with resistive load, max. | 0.5 A |
| on lamp load, max. | 5 W |
| Output voltage | |
| Rated value (DC) | 24 V |
| for signal "0", max. | 0.1 V; with 10 kOhm load |
| for signal "1", min. | 20 V DC |
| Output current | |
| for signal "1" rated value | 0.5 A |
| for signal "0" residual current, max. | 10 µA |
| Output delay with resistive load | |
| "0" to "1", max. | 50 µs |
| "1" to "0", max. | 200 µs |
| Total current of the outputs (per group) | |
| horizontal installation | |
| up to 50 °C, max. | 8 A; Current per mass |
| Relay outputs | |
| Switching capacity of contacts | |
| with inductive load, max. | 0.5 A |
| on lamp load, max. | 5 W |
| with resistive load, max. | 0.5 A |
| Cable length | |
| shielded, max. | 500 m |
| unshielded, max. | 150 m |
| Interrupts/diagnostics/status information | |
| Alarms | |
| Diagnostic alarm | Yes |
| Diagnostics indication LED | |
| for status of the outputs | Yes |
| Potential separation | |
| Potential separation digital outputs | |
| between the channels, in groups of | 1 |
| between the channels and backplane bus | 500 V AC |
| Degree and class of protection | |
| IP degree of protection | IP20 |
| Standards, approvals, certificates | |
| Ecological footprint | |
| environmental product declaration | Yes |
| Global warming potential | |
| global warming potential, (total) [CO2 eq] | 68.6 kg |
| global warming potential, (during production) [CO2 eq] | 8.16 kg |
| global warming potential, (during operation) [CO2 eq] | 60.7 kg |
| global warming potential, (after end of life cycle) [CO2 eq] | -0.334 kg |
| Ambient conditions | |
| Free fall | |
| Fall height, max. | 0.3 m; five times, in product package |
| Ambient temperature during operation | |
| min. | -20 °C; = Tmin (incl. condensation/frost); start-up @ 0 °C |
| max. | 60 °C; = Tmax |
| At cold restart, min. | 0 °C |
| Ambient temperature during storage/transportation | |
| min. | -40 °C |
| max. | 70 °C |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m |
| Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
| Relative humidity | |
| With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Resistance | |
| Coolants and lubricants | |
| Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air |
| Use in stationary industrial systems | |
| to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
| Use on ships/at sea | |
| to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
| to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
| Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
| Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| Conformal coating | |
| Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability |
| Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
| Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
| Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A |
| Connection method | |
| required front connector | Yes |
| Mechanics/material | |
| Enclosure material (front) | |
| Plastic | Yes |
| Dimensions | |
| Width | 45 mm |
| Height | 100 mm |
| Depth | 75 mm |
| Weights | |
| Weight, approx. | 220 g |
| Approvals / Certificates | |