6ES7231-4HA30-0XB0

6ES7231-4HA30-0XB0

SIMATIC S7-1200, аналоговий вхід, SB 1231, 1 AI, +/-10 В DC (роздільна здатність 12 біт) або 0-20 мА.

Категорія товару
Signal boards
Виробник
SIEMENS
Серія продуктів
S7-1200
General information
Product type designationSB 1231, AI 1x12 bit
Supply voltage
Rated value (DC)24 V
Input current
from backplane bus 5 V DC, typ.55 mA
Power loss
Power loss, typ.0.4 W
Analog inputs
Number of analog inputs1; Current or voltage differential inputs
permissible input voltage for current input (destruction limit), max.±35 V
permissible input voltage for voltage input (destruction limit), max.35 V
permissible input current for voltage input (destruction limit), max.40 mA
permissible input current for current input (destruction limit), max.40 mA
Cycle time (all channels) max.156.25 µs; 400 Hz suppression
Input ranges
VoltageYes; ±10V, ±5V, ±2.5V
CurrentYes; 0 to 20 mA
ThermocoupleNo
Resistance thermometerNo
ResistanceNo
Input ranges (rated values), voltages
-10 V to +10 VYes
Input resistance (-10 V to +10 V)≥9 MOhm
-2.5 V to +2.5 VYes
Input resistance (-2.5 V to +2.5 V)≥9 MOhm
-5 V to +5 VYes
Input resistance (-5 V to +5 V)≥9 MOhm
Input ranges (rated values), currents
0 to 20 mAYes
Input resistance (0 to 20 mA)≥ 250 Ohm
Analog outputs
Number of analog outputs0
Cable length
shielded, max.100 m; shielded, twisted pair
Analog value generation for the inputs
Measurement principleintegrating
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.11 bit; + sign
Integration time, parameterizableYes
Interference voltage suppression for interference frequency f1 in Hz40 dB, DC to 60 Hz
Smoothing of measured values
parameterizableYes
Step: NoneYes
Step: lowYes
Step: MediumYes
Step: HighYes
Errors/accuracies
Temperature error (relative to input range), (+/-)25 °C ±0.3%, to 55 °C ±0.6% total measurement range
Interrupts/diagnostics/status information
AlarmsYes
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Diagnoses
Wire breakNo
Diagnostics indication LED
for status of the inputsYes
for maintenanceYes
Standards, approvals, certificates
CE markYes
CSA approvalYes
UL approvalYes
cULusYes
FM approvalYes
RCM (formerly C-TICK)Yes
KC approvalYes
Marine approvalYes
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.-20 °C
max.60 °C
horizontal installation, min.-20 °C
horizontal installation, max.60 °C
vertical installation, min.-20 °C
vertical installation, max.50 °C
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Air pressure acc. to IEC 60068-2-13
Operation, min.795 hPa
Operation, max.1 080 hPa
Storage/transport, min.660 hPa
Storage/transport, max.1 080 hPa
Relative humidity
Operation at 25 ℃ without condensation, max.95 %
Pollutant concentrations
SO2 at RH < 60% without condensationS02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free
Connection method
required front connectorYes
Mechanics/material
Enclosure material (front)
PlasticYes
Dimensions
Width38 mm
Height62 mm
Depth21 mm
Weights
Weight, approx.35 g
Approvals / Certificates