6AG1232-4HA30-4XB0
SIPLUS S7-1200 SB 1232 1AQ на основі 6ES7232-4HA30-0XB0 із захисним лакуванням, -20…+60 °C, аналоговий вихід 1 AQ, +/-10 В DC (роздільна здатність 12 біт) або 0-20 мА (роздільна здатність 11 біт).
Категорія товару
Signal boardsВиробник
SIEMENSСерія продуктів
S7-1200| General information | |
|---|---|
| Product type designation | SB 1232, AQ 1x12 bit |
| based on | 6ES7232-4HA30-0XB0 |
| Input current | |
| from backplane bus 5 V DC, typ. | 15 mA |
| Output voltage | |
| Power supply to the transmitters | |
| Supply current, max. | 25 mA |
| Power loss | |
| Power loss, typ. | 1.5 W |
| Analog inputs | |
| Number of analog inputs | 0 |
| Analog outputs | |
| Number of analog outputs | 1 |
| Cycle time (all channels) max. | Voltage: 300 μS (R), 750 μS (1 uF) Current: 600 ms (1 mH); 2 ms (10 mH) |
| Output ranges, voltage | |
| -10 V to +10 V | Yes |
| Output ranges, current | |
| 0 to 20 mA | Yes |
| Load impedance (in rated range of output) | |
| with voltage outputs, min. | 1 000 Ω |
| with current outputs, max. | 600 Ω |
| Cable length | |
| shielded, max. | 100 m; shielded, twisted pair |
| Analog value generation for the outputs | |
| Conversion principle | Differential |
| Integration and conversion time/resolution per channel | |
| Resolution with overrange (bit including sign), max. | 12 bit |
| Errors/accuracies | |
| Temperature error (relative to output range), (+/-) | 25 °C ±0.5%, to 55 °C ±1% |
| Interrupts/diagnostics/status information | |
| Alarms | Yes |
| Diagnostics function | Yes |
| Diagnostics indication LED | |
| for status of the outputs | Yes |
| Ambient conditions | |
| Free fall | |
| Fall height, max. | 0.3 m; five times, in product package |
| Ambient temperature during operation | |
| min. | -20 °C; = Tmin (incl. condensation/frost) |
| max. | 60 °C; = Tmax |
| Ambient temperature during storage/transportation | |
| min. | -40 °C |
| max. | 70 °C |
| Altitude during operation relating to sea level | |
| Installation altitude above sea level, max. | 5 000 m |
| Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
| Relative humidity | |
| With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Resistance | |
| Coolants and lubricants | |
| Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air |
| Use in stationary industrial systems | |
| to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
| Use on ships/at sea | |
| to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
| to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
| Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
| Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| Conformal coating | |
| Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability |
| Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
| Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
| Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A |
| Mechanics/material | |
| Enclosure material (front) | |
| Plastic | Yes |
| Dimensions | |
| Width | 38 mm |
| Height | 62 mm |
| Depth | 21 mm |
| Weights | |
| Weight, approx. | 40 g |
| Approvals / Certificates | |